OSM Automatic Circuit Recloser 15kV & 27kV Models
Product Guide
PROTECTION
■ Directional over current and earth fault protection
• Current Setting Range 10-1280A
• Setting Resolution 1A
■ Inverse Time Protection
• 3 x Forward Direction Elements for each Trip in the Sequence independently settable for both over current and earth fault.
• 3 x Reverse Direction Elements for each Trip in the Sequence independently settable for both over current and earth fault.
• 4 xIEC255 Curves
• 8 xANSI Curves
• 2xUserDefined Curves
■ High set Instantaneous element
■ Definite Time Protection
• 0-120 seconds
• Time Resolution 0.01 seconds
■ Directional Sensitive Earth Fault Protection
• Current Setting Range 4-80A
• Setting Resolution 1A
• DefiniteTime 0-120 seconds
• Time Resolution 0.01 seconds
■ Under Voltage Protection
• Phase undervoltage balanced element (UV1)
- 3 phase load shedding
- Multiplier setting range: 0.6-1 of system voltage
- Multipliersetting resolution: 0.01
- Trip time range: 0-180 sec
- Trip time setting resolution: 0.01 sec
• Phase-to-Phase Undervoltage Element (UV2)
- Multiplier setting range: 0.6-1 of system voltage
- Multipliersetting resolution: 0.01
- Trip time range: 0-180 sec
- Trip time setting resolution: 0.01 sec
• Loss ofSupply(UV3)
- Trip time range: 0-180 sec
- Trip time setting resolution: 0.01 sec
- Reclose time: 0-180 sec
- Reclose time resolution: 0.01 sec
■ Under Frequency Protection
• Pickup Range: 45-50Hz (50Hz system), 55-60Hz(60Hzsystem)
• Frequency settings resolution: 0.01Hz
• Trip time range: 0-120 sec
• Trip time setting resolution: 0.01 sec
■ Voltage reclose control with automatic back feed restoration
Provides loop automation functionality.
Local Control Panel
■ Zone Sequence Co-ordination
■ Cold Load Pickup
• Cold load time ramp up: 1-400 min
• Cold load time ramp down: 0-60 min
• Cold load time resolution: 1 min
• Cold load multiplier: 1-5 times pickup current
• Cold load multiplier resolution: 0.1
■ Inrush Restraint
• Inrush time: 0.01-10sec
• Inrush time resolution: 0.01 sec
• Inrush multiplier: 1-20
• Inrush multiplierresolution: 0.1
■ Temporary TimeAddition
Provides a stepped time delay to automatically isolate faulted sections in a feeder or correct gradingofdevicesin series.
■ Duty Cycle
• O-0.1sec-CO-1sec-CO-1sec-CO-60sec
recoverytime
■ Dead Times
• 1stdeadtime range0.1 - 180seconds
• 2nd dead time range 1 -180 seconds
• 3rd dead time range 1 -180 seconds
• Setting resolution 0.01 seconds
■ Auto Reclose
• User configurable 1-4 trips to lockout, independently settable for overcurrent earth fault, sensitive earth fault and under voltage protection.