OSM Automatic Circuit Recloser 15kV & 27kV Models
Product Guide
Overview
The status of the recloser is also reflected by a microswitch connected to the control electronics. The electronic circuit board where the microswitch is fitted has no active elements which dramatically improves impulse immunity.
The main circuit bushings are manufactured from UV stable polymer and have a silicone rubber bushing boot to provide the required creepage distance.
The magnetic industrial actuators are operated from stored energy charged industrial capacitors located in the RC control cubicle. There is a rating plate located in the base of the tank that provides tank rating details in accordance with the requirements of ANSI C37.60. There is an earthing point on the side ofthe tank.
The 200 Series OSM is supplied with cable connectors on each bushing. These are made from tin plated brass and can take cable sizes up to 260mm2.
The cross sectional diagram below details the OSM tankconfiguration and main components.
The OSM automatic circuit reclosers incorporate vacuum interrupters inside a polycarbonate housing enclosed inside an arc vented stainless steel tank. This ensures the maximum in life and reliability with a fully insulated arrangement inside the long life housing.
Voltage is measured on all six (6) bushings using capacitively coupled conductive rubber screens. Current is measured on all six (6) bushings using Rogowski sensors. Three (3) bushings provide phase current measurements and the other three (3) bushings provide residual current measurement.
The recloser mechanism is operated by three (3) separate magnetic actuators, one per phase. These magnetic actuators are mechanically interlocked to guarantee correct three (3) phase operation. The device is latched in the closed position by magnetic latching. Each magnetic actuator uses a single coil and are the result of fourth generation development of magnetic actuators using remanence latching.
The recloser can be mechanically tripped using the yellow mechanical hook stick operated lever in the base ofthe tank.
The open and closed position of the device is indicated by a green '0' to indicate the device is open and a red 'I' to indicate the device is closed, also located in the base of the tank.
1. Bushing Connector
2. Silicone Rubber Bushing Boot
3. Polymer Bushing
4. Rogowski Coil Current sensor
5. Capacitively Coupled Voltage sensor
6. 304 Stainless Steel Tank
7. Magnetic Actuator
8. Opening Spring
9. Auxiliary Switches
10. Insulated Drive Rod
11. Polycarbonate Housing
12. Vacuum Interrupter
13. Ceramic Breather
14. Mechanical Trip Ring