| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | Emergency Cables | | | | | | | | | | Type designation S2XS2YFUG 1 x......RM .../... kV | | | | | | | | | | | | | | | | | | | | | Version | | 1 | 2 | 3 | 4 | | | | Rated voltage U0/U | kV | 64/110 | 76/132 | 127/220 | 160 /275 | | | | Max. working voltage U | kV | 123 | 145 | 245 | 300 | | | | Impulse withstand voltage | kV | 450 | 450 | 850 | 850 | | | | | | | | | | | | | | | | | | | | | Dimensions | | | | | | | | | | | | | | | | | | | | | | | Conductor, Cu | cross section | nom. | mm2 | 120 | 120 | 240 | 240 | | | | | diameter | approx. | mm | 12,8 | 12,8 | 18,3 | 18,3 | | | | XLPE insulation | | nom. | mm | 15 | 15 | 18 | 18 | | | | Screen, Cu wires | | nom. | mm2 | 25 | 25 | 35 | 35 | | | | Outer diameter | | approx. | mm | 59 | 59 | 69 | 69 | | | | Weight | | approx. | kg/m | 3,5 | 3,5 | 5,6 | 5,6 | | | | Bending radius | | min. | m | 1,2 | 1,2 | 1,4 | 1,4 | | | | | | | | | | | | | | | | | | | | | | | Electrical Data Conductor resistance | | | | | | max. Q/km approx. Q/km | | | | | | DC at 20°C AC at 90°C | | | 0,153 0,196 | | 0,153 0,196 | | 0,0754 0,0971 | | 0,0754 0,0971 | | | | | | | | | | | | | | | | | | | | | | Capacitance per core Transmission Capacity Current rating (continuous)/Power rating | | | | | | approx. |jF/km 0,126 0,126 0,134 0,134 laid on ground, 7 cm spacing between cables A/MVA 420/80 420/96 650/248 650/310 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|