Model 3030F Batch Controller Indicator/Totalizer
Description
Indicates rate, total, and provides single or dual stage batch control. Two parameters can be simultaneously displayed. The unit contains two process inputs, five control inputs, and four control outputs. A user-friendly menu system provides scrolling help messages to make programming simple when changes are required. The unit contains a set point lock out system to prevent unauthorized changes from the front panel and a 10-year memory backs up all program settings and flow parameters in case of a power failure. The unit can be factory programmed for your application. Use with Aaliant and Niagara's Target, Nutating Disc, Oscillating Piston, Turbine flowmeters.
Technical Information
Functional Specifications
Power Supply
18 to 27 VDC/6 Watts max, 0.4 Amps max and
1 phase 50/60 Hz 115/230 VAC +10% - 15%/0.2/0.1 Amps
Accessory Power
Only if unit is AC powered/24 VDC + 5%/100 mA max
Temperature
Operating: 32° F to 131° F (0° C to 55° C) Storage: - 40° F to 158° F (- 40° C to 70° C)
Display Outputs
Two parameters simultaneously
Display diqits
6 for Rate, 10 for Total, 6 for Batch, 3 for alphabetical characters
Flow Inputs
Type
Current sinking (contact closure or npn transistor to ground)
Impedance
5.8 Kfi pull-up resistor to + 5 VDC
Logical Voltages
0.0 to 2.2 VDC low, 2.8 to 24 VDC high
Response
0 to 40 Hz max with 10 msec minimum pulse width 0 to 400 Hz max with 1.5 msec minimum pulse width 0 to 7.5 KHz max with 50 usec minimum pulse width
Input A
Flow
Input B
Flow input inhibit (flow input ignored when pulled low)
Start
Batch Controller: disabled, only start, or reset batch count and start
Rate Meter: No function
Totalizer: none, reset totalizer count, unlatch totalizer set point output, or reset totalizer count and unlatch totalizer set point output
Reset
Batch Controller: none, reset batch count, unlatch batch overrun set point output, or reset batch count and unlatch batch overrun set point output Rate Meter: none, or unlatch rate hi/lo set point outputs Totalizer: none, reset totalizer count, unlatch totalizer set point output, or reset totalizer count and unlatch totalizer set point output
Stop
Batch Controller: only stop, or stop and unlatch batch overrun
set point output Rate Meter: none, or unlatch rate hi/lo set point outputs Totalizer: no function
Control Inputs
Qty
5
Type
Current sinking (contact closure or npn transistor to ground)
Impedance
5.8 Kfi pull-up resistor to + 5 VDC
Logical Voltages
0.0 to 1.0 VDC low, 3.5 to 24 VDC high
Response
30 msec input
Control Input 1
Use: Batch start
Control Input 2
Use: Reset batch count and unlatch batch overrun set point output, unlatch rate hi/lo set point outputs, and unlatch totalizer set point output
Control Input 3
Use: Batch stop
Control Input 4
Use: Batch jog
Control Input 5
Use: Unlatch batch overrun set point output, unlatch rate hi/lo set point outputs, and unlatch totalizer set point output
Figure 1. Model 3030FW Batch Controller Indicator/Totalizer