Model 1030F
Description
Indicates rate, total, and set points. Rate and total can be simultaneously displayed. The unit contains two process inputs, five control inputs, one current and four control outputs. A user-friendly menu system provides scrolling help messages to make programming simple when changes are required. The unit contains a set point lock out system to prevent unauthorized changes from the front panel and a 10-year memory backs up all program settings and flow parameters in case of a power failure. The unit can be factory programmed for your application. Use with Niagara's Nutating Disc, Oscillating Piston, and Turbine Flowmeters.
Technical Information Functional Specifications
Power Supply
18 to 27 VDC/6 Watts max, 0.4 Amps max or
1 phase 50/60 Hz 115/230 VAC +10% - 15%/0.2/0.1 Amps
Accessory Power
Only if unit is AC powered/24 VDC ± 5%/100 mA max
Temperature
Operating: 32° F to 131° F (0° C to 55° C) Storage: -40° F to 158° F (-40° C to 70° C)
Display Outputs
Two parameters simultaneously
Display digits
6 for Rate, 10 for Total
Flow Input A
Type
Current sinking (contact closure or npn transistor to ground)
Impedance
5.8 KQ pull-up resistor to + 5 VDC
Logical Voltages
0.0 to 1.3 VDC or 2.8 to 24 VDC
Response
0 to 40 Hz max with 10 msec minimum pulse width 0 to 400 Hz max with 1.5 msec minimum pulse width 0 to 7.5 KHz max with 50 usec minimum pulse width
Inhibit Flow Input B
Type
Current sinking (contact closure or npn transistor to ground)
Flow input ignored when pulled low
Impedance
5.8 KQ pull-up resistor to + 5 VDC
Logical Voltages
0.0 to 1.3 VDC low, 2.8 to 24 VDC high
Control Inputs
Qty
5
Type
Current sinking (contact closure or npn transistor to ground)
Impedance
5.8 KQ pull-up resistor to + 5 VDC
Logical Voltages
0.0 to 1.0 VDC low, 3.5 to 24 VDC high
Response
30 msec input
Control Input 1
Use: Unlatch totalizer set point output
Control Input 2
Use: Reset totalizer count
Control Input 3
Use: Unlatch rate hi/lo set point outputs
Control Input 4
Use: Unlatch totalizer set point output and unlatch rate hi/lo set point outputs
Control Input 5
Use: Reset totalizer count, unlatch totalizer set point output, and unlatch rate hi/lo set point outputs
Analog Output
Type
4-20 mA isolated
Voltage
12 to 27 VDC
Response
0.5 seconds
Accuracy
± 0.1 % at 25° C/± 0.25 % over temperature range
Resolution
0.05% (11 bits)
Control Outputs
Qty
4
Type
Current sinking (npn transistor to ground)
Rating
150 mA @ 30 VDC blocking maximum
Figure 1. Model 1030FW Indicator/Totalizer
(864) 574-3327 (800) 778-9251 Fax: (864) 574.8063 www.venturemeas.com/niagara niagarasales@venturemeas.com