Text version of the page
NESLAB ThermoFlex
™ 1400 Specifications Product Specfications
Setpoint Temperature Range 5°C - 40°C 41°F - 104°F Ambient Temperature Range 10°C - 40°C 50°F - 104°F Temperature Stability +/- 0.1°C Setpoint Cooling Capacity at 20°C (see graph below for cooling curves) 60 Hz 1400W (4778 BTU)
50 Hz 1170W (3995 BTU) Reservoir Volume Gallons 1.9 Liters 7.6 Compliance NRTL Certified to CSA and UL Standards; CE-Marked Footprint or dimensions (HxWxD) Inches 27.4 x 14.2 x 24.7 cm 69.6 x 36.1 x 62.7 Power options Unit Weight Option 1100V/50Hz/1 Phase 20ACircuit
Option 2100V/60Hz/1 Phase 20ACircuit
Option 3115V/60Hz/1 Phase 20ACircuit
Option 4208-230V/60Hz/1 Phase 15ACircuit
Option 5230V/50Hz/1 Phase Amp 16ACircuit lb 126 kg 57.2 Pumps (see graph below for performance curves) PD 1 - Positive Displacement
60 Hz 2.1 gpm @ 60 psi
50 Hz 1.7 gpm @ 60 psi
PD 2 - Positive Displacement
60 Hz 4.1 gpm @ 60 psi
50 Hz 3.3 gpm @ 60 psi >
Cooling CapacityPumping Capacity
Specifications obtained at sea level using water as the recirculating fluid, at a 20°C process setpoint, 25°C ambient condition, at nominal operating voltage. Other fluids, fluid temperatures, ambient temperatures, altitude or operating voltages will affect performance. Thermo Electronreserves the right to change specifications without notice. Pump performance results obtained with no restrictions on return to the system.