TECHNICAL INFORMATION SHEET:
NEMOTO NP-ANS Single Header Ammonia Pellistor Gas Sensor
General Description
The Nemoto NP-ANS is a catalytic (pellistor) type
flammable gas sensor supplied as a matched pair of
pellistor elements mounted on a single header and
protected by a metal mesh enclosure and can.
Designed as a single header, lower cost sensor, the
NP-ANS is optimised for the detection of ammonia
in air in range 0-100% LEL but is stable and
sensitive enough to be used for ranges as low as 0-
5,000ppm, with alarm levels as low as 2,000ppm
without false alarms, provided good quality circuitry
is employed.
A feature of the NP-ANS is its very high selectivity
to ammonia, the sensitivity of the device to
hydrocarbon gases being negligible.
The highly automated manufacturing procedure
employed by Nemoto results in a repeatable reliable
sensor which, unlike similar devices, requires no
trimming resistor to enable the detector to be
matched with a compensator.
Specifications:
Recommended Voltage: 2.2V +/- 0.1V
Current Drawn: 175 +/- 15mA
Zero Offset: 0mV +/- 30mV
Gas Sensitivity: 23 - 45mV/% NH3/Air
Maximum Range: 0-50% LEL
Minimum Range: 0-5000ppm
Accuracy: +/- 200ppm(NH3)
Maximum Long Term Drift:
Span: < +/- 5% Signal/Month
Zero: <+/- ˝ mV/Month
Response Time: T50: 3 sec T90: 8 sec
Recommended
Circuit:
Note: The value R1 is arbitrary, since the function of R1 is
to balance the bridge. 200 - 1K is suggested.
Temperature Range: -20°C to +60°C
Temperature Drift: (-20°C to +70°C)
Zero: < +/- 2%LEL
Humidity: 0-100%RH, non-condensing
Humidity Response: +/- 2%LEL
Linearity: Effectively Linear to 50%LEL
Test data on drift, poisoning, temperature
performance, linearity is available on the
Characterisation Document np-ans-CD.doc
Nemoto has a policy of continuous development and
improvement of its products. As such the specification for the
device outlined in the data sheet may be changed without notice
ds-npans.doc, issue 3, May 2008
|
|