Data Sheet : Press Man

MO TRON

Description Picture

Press Man is a simple but yet efficient controller for maintaing constant pressure in heating and ventilation environments. It is charactized by a very robust construction and extremely simple user interface. controls the HVAC pressure from an pressure transmitter with an analog output mounted directly in the ventilation system. Difference pressures can be obtained by incorporating mecanical blends etc. IP54 grade and integrated keys / display makes Press Man well suited for many applications. Press Man

MO TRON

has a setpoint, which is controlled by the arrows. A single press will put the setpoint one up or down, holding the arrows will make the setting change fast while pressed. Measured pressure will be displayed apr. 5 sec after keys have been released
PRESS MAN Press Man Press Man has two relay outputs, the first is used on ON/OFF by the key setting, the other is used for alarming. ON/OFF is activated as the key is activated, the alarm output will be active when the output can not be reached whithin 30 minutes !. Means, that if the output internally is UNDER or OVER the MIN/MAX settings, the relay will activate. Flashing LO or HIGH in display Press Man can indicate the real output for the attached speed controller, OR, it can indicate the real input from the attached pressure transmitter. Both values will indicate in percentage (0-100) of input and output) Press man
ONOFF can be 100% stopped, pressing the ON/OFF button. Display will indicate OFF and the DC output will be forced to 0, as will be the 2 relays. Press man PRESS MAN can be SCALED to one of 4 ranges by POWER UP. This will make it very useful for different industrial pressure transmitters on the market today. It will be compatible with Motron PS1000 scaleable pressure transmitter. It comes with an standard ac/dc supply interface, 0-10V output and dipswitch settings for 150 - 300 - 500 - 1000 Pa
SHOWOUT PBAND SHOWIN has individual settings for minimum and maximum speed for the attached speed controller. Settings to be controlled by MIN/MAX buttons. Parameters for Proportional Band and Integration Time is done from the keypads as any other parameter. The PI regulator will meassure the pressure, compare it to the setpoint and try to maintain the dc output to make the real pressure as close to the setpoint as possible. On power up, version and range information is presented shortly in display.
MINOUT ITIME MAXOUT 1x230V ~ 50/60Hz Max 2A

Technical data Keys etc

Indicates settings, pressurealarms and OFF status ON/OFF switchBy OFF DC output will be forcedto zero, as well as relay 1 and 2 will be offIndicating PI regulatorDOWN regulatingSETPOINT adjustment by single key User interface from front. 230 +/- 15 VAC / 50Hz supply Two Relay outputs 2A / 230VAC
MO TRON
PRESS MAN Two temperature inputs, non active Two 0-10V Inputs – only one used for transmitter
A ll other settings by combined keys Two Analog outputs 0-10V / 10mA -one used
HOLD FOR 2 SEC ON POWER UP SCALES INPUT TO 500 PA FOR 0-10V HOLD FOR 2 SEC ON POWER UP SCALES INPUT TO 150 PA FOR 0-10V Auxillary DC supply out 24VDC / 20mA +/- 30%
ONOFF Environmental temperature -5 – 45ºC Humidity 5-95% RH, non condensing
Indicates output voltageto speed controller in percentageIndicates input voltage frompressure transmitter in percentageSetting of minimum outputvoltage for speed controller in percentage SHOWOUT PBAND SHOWIN LED indicating UP or DOWN regulation
Setting of maximum outputvoltage for speed controllerin percentage Industrial cable glands for connection
MINOUT ITIME MAXOUT Industrial IP54 grade
HOLD FOR 2 SEC ONPOWER UP SCALES INPUTTO 300 PA FOR 0-10V 1x230V ~ 50/60Hz Max 2A HOLD FOR 2 SEC ONPOWER UP SCALES INPUTTO 1000 PA FOR 0-10V Polycarbonate plastic case Polycarbonate front with integrated keys
Setting of Integration Time in the PI Regulator Setting of Proportional Band in the PI Regulator Connection through ”snap" terminals
!! KEYS LOCKED !!! EMC 89/336/EEC LVD 73/23/EEC
No settings can be performed before the Un Lock sequence has been carried out. This will ensure unattemtedchanging of parameters from unauthorized personel.Pressing of SHOW OUT and SHOW IN for 10 secondswill unlock Press Man for 10 minutes (automatically returns to LOCK)Display will indicate LOC while lock is on. Indicating PI regulatorUP regulatingSETPOINT adjustment by single keyAll other settings by combined keys (EN 50081-1, EN50082-2) CE approved. Meassures 130x80x60 mm

Connetions

PRESSURETRANSMITTER0-150 Pa0-300 Pa 0-500 Pa 0-1000 Pa

Functions

+24V AUX0V/Gnd 0-10V IN 1 0-10V IN 20V/GndTEMP IN 20-10V OUT 10-10V OUT 2 NL1 230V AC RELAY 1NONO TEMP IN 10V/Gnd TRAFO KEYBOARD 0V/Gnd ALARMOUTPUTON/OFFOUTPUT RELAY 2NONO RELAY 1 RELAY 2 SPEED CONTROLLER +100%PI Output0% 10VDC Output for speed controllerMAXOUTMINOUT