KEY DESCRIPTION DISPLAY COMMENT/DEFAULT General setting of parameters. Press to activate with other keys Depends on function chosen Beep by press >
SETPOINT Setpoint adjustment for RH controller, DCouts / Relay out 5 – 95 % RH 0.1 %RH / press 50 %RH ab Fabric >
LOW Low limit for relay Could be alarm or
Industrial humidifier (2% hysterese) 5 – High Limit minus 5 %RH 0.1 %RH / press 20 %RH ab Fabric >
HIGH High limit for relay Could be alarm or De humidifier (2% hysterese) Low Limit plus 5 – 95% RH 0.1 %RH / press 80 %RH ab Fabric >
P BAND Proportional band for regulator Affects both 0-10V potputs 0-50 %RH 1 %RH / press 10 % RH ab Fabric 0 = NO P band !! >
ITIME Integration time for regulator Affects both 0-10V potputs 0-50 Seconds 1 sec / press 10 sec ab Fabric 0 = NO I time !! >
MIN HOLDING for 5 seconds ! Displays LOWEST %RH since Last zeroing or power up 0-100 % RH Initializing at power up Displays MIN input from
humidity sensor Reset to Actual %RH by >
MAX HOLDING for 5 seconds ! Displays HIGHEST %RH since Last zeroing or power up 0-100 %RH Initializing at power up Displays MAX input from humidity sensor Reset to Actual %RH by >