Catalogue Motron - Controls
www.motron.dk
print switch display
Page / 10
Motron - 5032, 2090, 16074
/ 10
See other catalogues for Motron
Text version of the page

Programming of Air Man Humidity controller

KEY DESCRIPTION DISPLAY COMMENT/DEFAULT General setting of parameters. Press to activate with other keys Depends on function chosen Beep by press
SETPOINT Setpoint adjustment for RH controller, DCouts / Relay out 5 – 95 % RH 0.1 %RH / press 50 %RH ab Fabric
LOW Low limit for relay Could be alarm or Industrial humidifier (2% hysterese) 5 – High Limit minus 5 %RH 0.1 %RH / press 20 %RH ab Fabric
HIGH High limit for relay Could be alarm or De humidifier (2% hysterese) Low Limit plus 5 – 95% RH 0.1 %RH / press 80 %RH ab Fabric
P BAND Proportional band for regulator Affects both 0-10V potputs 0-50 %RH 1 %RH / press 10 % RH ab Fabric 0 = NO P band !!
ITIME Integration time for regulator Affects both 0-10V potputs 0-50 Seconds 1 sec / press 10 sec ab Fabric 0 = NO I time !!
MIN HOLDING for 5 seconds ! Displays LOWEST %RH since Last zeroing or power up 0-100 % RH Initializing at power up Displays MIN input from humidity sensor Reset to Actual %RH by
MAX HOLDING for 5 seconds ! Displays HIGHEST %RH since Last zeroing or power up 0-100 %RH Initializing at power up Displays MAX input from humidity sensor Reset to Actual %RH by