2/16 Technical Data XVC100
Moeller HPL0213-2004/2005 XVC-101-C192K-K82 General Ambient temperature Operation°C -0 – +60Storage°C -25/85Relative humidity, non-condensing (IEC/EN 60068-2-30)% 10 – 95Noise immunity EN 61000-6-2Emitted interference EN 50081-2, Class AProtection >
Embedded HMI-PLC Front (NEMA 12) IEC/EN 60529 IP65Rear IP20Weightkg Approx. 0.9
Power supply specification Nominal valueV 24 V DC SELV, safety extra-low voltageRated voltage U >
e V DC 24 V DC to DIN 19240Admissible rangeV Voltage dips Max. 100 ms (at 20.4 V DC to 0 V DC, repetition rate: 1 s)Protection against polarity reversal YesProtective element YesFuseA 2, slowBreaking capacityA 30Electrical isolation No, 0 V connected to enclosure potential (GND)Current consumptionmA Normally 160Power consumptionW Normally 4 Real-time clock
Industrial counter Seconds, minutes, hours, day, month, year, decadeLeap year conversion AutomaticallySummer time conversion By means of softwareDeviation at T >
amb = 25°C Normally g 100 ppm Display Type Passive matrix mono LC display (mono STN LCD yellow-green)ResolutionPixels 128 x 64Display areamm 71 x 39Back-lighting LED Operation Membrane keypad 28 keys; 3 LED'sCompact flash card Type 1, ATA flash, 5 V Interfaces Programming interface RS232, not potential-free (D sub-miniature 9-pole male)Communication interface CAN, not potential-free (D sub-miniature 9-pole male) X1 plugs (digital inputs, outputs) Number of digital I/Osoff 8Qty. of
professional feeder connections 1Qty. of 0 V connections 1Power supply OutputsV DC Normally 24Admissible rangeV DC 18.5 – 30.2Max. output current per channelA 0.5Inductive loads Max. 150 mJInput voltage High level U >
H –3/4.5 V DCLow level U >
L –3/4.5 V DCMaximum input voltageV DC 40Input current High level I >
H 2 – 15 mALow level I >
L 0 – 1 mA >