mayr
Spark Quenching Unit Type 070.000.6
Application
Reduces spark production on the switching contacts occurring during VDC inductive load switching.
• Voltage limitation according to VDE0580 2000-07, Item 4.6.
• Reduction of EMC-disturbance by voltage rise limitation, suppression of switching sparks.
• Reduction of brake engagement times by a factor of 2-4 compared to free-wheeling diodes.
E189728 V V
Function
The spark quenching unit will absorb voltage peaks resulting from inductive load switching, which can cause damage to insulation and contacts. It limits these to 70 V and reduces the contact load. Switching products with a contact opening distance of > 3 mm are suitable for this purpose.
Dimensions (mm)
Electrical Connection (Terminals)
1 (+) Input voltage
2 (-) Input voltage
3 (-) Coil
4 (+) Coil
5 Free nc terminal
6 Free nc terminal
34
19
25
5
in
CO
t---
o
CO
Technical Data
Input voltage
max. 300 VDC, max. 615 V .
' peak
(rectified voltage 400 VAC, 50/60 Hz) max. 9 J/2 ms max. 0,1 Watt
250 V
IP65 / IP20 terminals -25 °C up to +85 °C -25 °C up to +105 °C
2,5 mm2 / AWG 26-12
Switch-off energy Power dissipation Max. voltage nc terminals Protection
Ambient temperature Storage temperature Max. conductor connection diameter
Max. terminal tightening torque 0,5 Nm
Accessories
Mounting bracket set for 35 mm rail acc. to EN50022 Article-No. 1803201
Order Number
/0 7 0.0 0 0.6
A