Marsh Bellofram Diversified Electronics Division TDD/TUD Series OFF-Delay Relay Output - Marsh Bellofram - #1 |
|
You may also be interested in
Sensor, Thermocouple type K, Detector, Thermometer, High precision regulator
Text version of the page
800.727.5646 atcdiversified.com Diversified Electronics TDD/TUD Series
Time Delay Relays // TDD/TUD Series
71
OF F -Dela y R e l a y Ou t p ut
Voltage is continuously applied to the input. An external isolated switch
controls the timer. When closed, the relay energizes. Opening the switch
initiates the delay period. Upon completion of the delay period, the relay
de-energizes. If the control switch recloses during the delay period, the
relay remains energized and the timer resets to zero.
SUPPLY VOLTAGE
OUTPUT
CONTROL SWITCH
TIME DELAY
RB-11/PF113A RB-08/PF083A 70-463-1
\\\WIRING
\\\DIMENSIONS (INCHES)
\\\SPECIFICATIONS
TIMING RANGES Virtually unlimited. See page 84 for
standard ranges available.
OUTPUT
RATING
DPDT 10 A @ 250 VAC or 24 VDC, resistive;
211 VA @ 120 VAC, inductive
SPDT 10 A @ 120 VAC, resistive; 211 VA
@ 120 VAC, inductive
TIMING
TOLERANCES
Minimum
Setting +0–20%
Maximum
Setting ±10%
REPEATABILITY 1% maximum; no first cycle effect
RESET TIMES
Before Time
Out 100 mSEC
After Time
Out 50 mSEC
RECYCLE TIME 40 mSEC
SUPPLY
VOLTAGE 24 or 120 VAC or VDC, 50/60 Hz; ±10%
FALSE TRANSFER No
REVERSE
POLARITY
PROTECTED
Yes
POWER
CONSUMPTION 3 watts (approximately)
DUTY CYCLE Continuous
TEMPERATURE
RATING
Operate 32° to 131°F (0° to +55°C)
Storage -49° to 185°F (-45° to +85°C)
LIFE
EXPECTANCY
Mechanical 10 million operations (minimum)
Electrical 100,000 operations @ rated load
WEIGHT 6 oz.
MODEL NUMBER >>>>>> T D A
Series
D
24
K
A
Relay output
Relay Output with CSA U*
Supply Voltage
24 Volts AC or DC
110/120 Volts AC or DC 120
Type of Operation
Knob Adjustable
Lock Nut Adjustable L
Fixed F
External Resistor Adjustable R**
Enclosure Style
8 or 11-pin octal plug-in
Blade plug-in B
Delay Period
See page 84 for standard ranges available
Example:
TDD-120-AKA-600—Delay on Release, 120 Volts AC or DC, knob adjustable from
6 to 600 seconds, 11-pin octal plug-in UL Recognized.
Notes:
* The TUD series is offered in 120 Volts, octal plug-in (figure 17) style A enclosure only with
optional types of operation K, L, or F. CSA certified: File #LR40123
** TDD’s using the “R” option are not UL Recognized. The “R” option is NOT offered in the
TUD series or the style B enclosure.
\\\OPERATION
|
|