Marsh Bellofram Diversified Electronics Division SLH Series Phase and Under Voltage Monitor with Adjustable Hysteresis - Marsh Bellofram - #1 |
|
You may also be interested in
Digital indicator, Voltage detector, Pressure transducer, Pneumatic regulator, Time-clock
Text version of the page
800.727.5646 atcdiversified.com Diversified Electronics SLH Series
Phase Voltage Monitors // SLH Series
225
Phase, Under Vol tage Mo n i t or wi t h A d j . H y s t e r e s i s
The SLH Series is designed to protect equipment against PHASE LOSS
(single phasing), UNDER VOLTAGE (brown outs), and PHASE REVERSAL
(improper sequence).
When correct phase sequence and line voltage are present, the internal
relay of the SLH will energize (PICK UP). When there is a phase
loss, under voltage or phase reversal condition, the internal relay will
de-energize (DROP-OUT). When conditions return to normal, the SLH
will automatically reset.
The SLH is unique in that it has a field-adjustable hysteresis. The voltage
setting is adjusted to the desired pick-up point indicated by the dial
setting. Then, the hysteresis adjustment is set to the desired percentage to
achieve the preferred drop-out point. When models up to 300 VAC are set at
0%, they will pick-up and drop-out at the same point, when set at 10%, the
drop-out will be an average of the phase-to-phase voltages 10% below the dial
setting pick-up point. Models over 300 VAC are adjustable from 0% to 15%.
The SLH is available in the standard voltage ranges (see table below). It has an LED
indicator that glows when all conditions are normal. The SLH Series is UL Listed under UL
File Number E55826.
\\\OPERATION
\\\SPECIFICATIONS
OPERATING
VOLTAGE See Table Below
POWER REQUIRED See Table Below
RESET Automatic
PHASE SEQUENCE ABC (Will Not Operate CBA)
HYSTERESIS
Models Up to
300 VAC
Adjustable, 0% to 10%
Below Pick-up
Models Over
300 VAC
Adjustable, 0% to 15%
Below Pick-up
OUTPUT RATING
Models up to
300 VAC
DPDT, 10 Amps @ 120 VAC,
Resistive; 211 VA @ 120 VAC,
Inductive
Models Over
300 VAC
DPDT, 5 Amps @ 240 VAC,
Resistive; 345 VA @ 240 VAC,
Inductive
TERMINATIONS (12) #8-32 Screw Terminals
INDICATORS LED Glows When All Conditions Are Normal
RESPONSE TIMES See Table Below
TEMPERATURE
RATING
Operate 32° to +131°F (0° to +55°C)
Storage -49° to 185°F (-45° to +85°C)
WEIGHT 14 oz.
\\\DIMENSIONS (INCHES)
\\\WIRING
MODEL
NUMBER PICK UP VOLTAGE
RESPONSE TIMES
OPERATE RELEASE POWER REQUIRED
SLH-120-ALE 95-130 V. Adj. 80 m. SEC 0.5 SEC 3 VA
SLH-230-ALE 190-270 V. Adj. 150 m. SEC 0.5 SEC 3 VA
SLH-440-ALE 430-480 V. Adj. 1.0 SEC 2.0 SEC 7 VA
All voltage referenced are phase-to-phase.
|
|