Power supply · regulated, 120 W

Primary switchmode power supply, PFC, Single-phase, screw terminal - pluggableInput: Wide range input AC 93 - 132 V; DC 186 - 264 V, DC 210 - 370 V - adjustableOutput: 12 V / 24 V / 48 V - adjustable

DescriptionPart-No.TypePU Screw terminal Output voltage/currentDC 12 V; 10 A722770DRA 120-12FPB1 DC 24 V; 5 A 722758 DRA 120-24FPB 1DC 48 V; 2.5 A722777DRA 120-48FPB1 InputDRA 120-12FPBDRA 120-24FPBDRA 120-48FPB Voltage AC 115 / 230 V (manual switch) Operation voltage rangeAC 93–132 V; AC 186–264 V / DC 210–370 V Line frequency 47–63Hz Rated currentV
in = 115 V; AC: 1.25 A / V
in = 230 V; AC: 0.63 A Inrush current V
in = 115 V; AC: 24 A / V
in = 230 V; AC: 48 mA Input fuseT4A / AC 250 V internal Power Factor Correction P.F.C. 0,7

Dimensions PIN assignment Derating Parallel mode

Output
61 116[4.57]10.0[0.39] Rated voltage output DC 12 V DC 24 V DC 48 V
DCOUTPUT Rated current output10 A5 A 2.5 A
--++ Rdy Voltage trim range 11.4–14.5 V 22.5–30 V 45–55 V
VoutADJ. DCLODCON Accuracy±1 %
115VAC230VAC Line regulation ±0.5 %
125[4.92]142[5.59] Load regulationSingle ±1 %, Parallel ±5 %
NL Transient recovery time 1.0 ms
ACINPUT Temperature coefficient±0.3 % / °C
63.5[2.5] Ripple & Noise 50mV
79 Hold up timeV
in = 115 V: 25 ms / V
in = 230 V: 30 ms Status indication DC ON (LED green) 10–11 V 21–22 V 42–44 V Status indication DC LOW (LED red)<10–11.2 V20.5/22.5 V<41–45 V Parallel mode max. 3 units Efficiency84 %86 %87 % Rated over load protection 105–125 % Over voltage protection125–145 % Short circuit characteristics Current limit General Switching frequency min. 80 kHz Isolation voltage input/output3kVeff Isolation resistance at DC 500 V 100M Operation temperature range-10°C – 70°C (Derating) Derating -2.5% / °C starting at 61 °C Storage temperature range-25°C–85°C M.T.B.F. 210000h Relative humidity20–90% RH Dimensions 63.5×142.0×116.0mm CoolingAir convection Housing material metal Field installationrail TS 35 (EN 50022) Installation postition vertical IP ratingIP20 Protection class – Weight (per unit)0,86kg/ 1.895 lbs Termination Screw terminal: 0.2–2.0 mm
2 ApprovalsUL: UL 508 listedcUL: UL 60950-1TÜV: EN 60950CE: EN 50081-1; EN 55022 Class BEN 6100-3-2, EN 6100-3-3, EN 50082-1, EN 55024 Monitoring DC ON Control (Rdy)–Normally open– Switching voltage – DC 60 V – Switching current–max. 300 mA– Switcing capacity – Isolation voltage–DC 500 V–

14

DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
page 16 p.16
page 17 p.17
page 18 p.18
page 19 p.19
page 20 p.20
page 21 p.21
page 22 p.22
page 23 p.23
page 24 p.24