You may also be interested in
Electrical enclosure, Load-break switch, Connector, Disconnect switch, Distribution panel
Text version of the page
a~í~=pÜÉÉíFuse Distribution Cabinet Data Sheet - 20919 Fuse Distribution CabinetcìëÉ=aáëíêáÄìíáçå=`~ÄáåÉíaÉëáÖå=cÉ~íìêÉë•Designed for external & internal applications. ?6, 8 & 9-way single cabinet options (up to 14 outgoing ways available, 2 cabinet design). ?800 amp, 1600 amp & 2250 amp main busbar rating. ?800 amp, 1600 amp & 2250 amp 3-phase 4-wire pole operated incoming off-load isolator. ?630 amp rated triple pole outgoing circuits with provision for BS88 JS type 92mm fuse links as per ENATS 37.2. ?800 amp & 1600 amp 3-phase off-load outgoing isolator circuits. ?800 amp & 1250 amp MCCB outgoing ways. ?Metering available to suit customer’s specification. ?Fully sheilded internally to IPXXB. ?Tested in accordance with ENATS 37.2. Lucy Switchgear, Howland Road, Thame, Oxfordshire OX9 3UJ, United Kingdom. Tel: +44 (0)1844 267267, Fax: +44 (0)1844 267223, Email: switchgear.sales@wlucy.co.uk, Internet: http://www.lucyswitchgear.com= Data Sheet March 2006 LDS10-004 - Issue 1 1 |
|