| | | Motor protection circuit breakers With thermal and magnetic trip releases | | |
| | | -3 | | |
| | | _electric | | |
| | | |
| | | |
| | | |
| | | Motor protection circuit breakers SM2A-SM3A up to 100A | | | | | | | | | | | | | Order | Short circuit | Short circuit | Qty | Wt | | | | code | thermal | breaking | per | | | | | | trip | capacity | pkg | | | | | | adjustment | at 400V | | | | | | | range | Icu | Ics | | | | | | | [A] | [kA] | [kA] | n° | [kg] | | | | Breaking capacity Icu 50kA at 400V. | | | | 11 SM2A 64 | 22-32 | 50 | 25 | 1 | 0.960 | | | | 11 SM2A 68 | 28-40 | 50 | 25 | 1 | 0.960 | | | | 11 SM2A 72 | 36-45 | 50 | 25 | 1 | 0.960 | | | | 11 SM2A 76 | 40-50 | 50 | 25 | 1 | 0.960 | | | | | | | | | | | | | |
| | | General characteristics The SM2A and SM3A types are circuit breakers with a wide adjustment range, 22 to 100A, in only two frame sizes enabling motor control and protection up to 45kW (400V). A magnetic trip indicator and padlockable operating handle are integrated on the SM2A and SM3A breakers. Both are suitable for isolation according to IEC/EN 60947 standards. Their high breaking capacity consents to exclude protection fuses on the majority of the installations. | |
| | | |
| | | |
| | | Operational characteristics - Rated insulation voltage Ui: 690V
| | |
| | | |
| | | Breaking capacity Icu 50kA at 400V. | | |
| | | |
| | | |
| | | | | | | | | | | | | | 11 SM3A 84 | 45-63 | 50 | 25 | 1 | 2.100 _ | | | | 11 SM3A 88 | 57-75 | 50 | 25 | 1 | 2.100 | | | | 11 SM3A 92 | 70-90 | 50 | 25 | 1 | 2.100 _ | | | | 11 SM3A 96 | 80-100 | 50 | 25 | 1 | 2.100 | | | | | | | | | | | | | Rated impulse withstand voltage: 6kV Rated frequency: 50/60Hz Maximum rated current: 50A (SM2A) and 100A (SM3A) Number of adjustment ranges: SM2A: 4 (22 to 50A) SM3A: 4 (45 to 100A) | | |
| | | |
| | | Breaking capacity: See table below Power dissipation: SM2A: 7.1-20W SM3A: 10-38W Magnetic tripping: 13In max Thermal tripping class: 10 Phase failure sensitive | | |
| | | 11 SM2A... | | |
| | | |
| | | |
| | | Life (cycles): Mechanical SM2A 50,000 SM3A 50,000 | | Electrical (le AC3) 25,000 25,000 | | |
| | | |
| | | Mounting: SM2A - Screw fixing or on 35mm DIN rail (IEC/EN 60715) SM3A - Screw fixing or on DIN rail 35mm (IEC/EN 60715) or 75mm (IEC/EN 60715) Mounting position: Any Utilisation category: A Degree of protection: IP00. | | |
| | | |
| | | Certifications and compliance Certifications obtained: cuius, CSA. Compliant with standards: IEC/EN 60947-1, IEC/EN 60947-2, IEC/EN 60947-4-1. NOTE: When more than one breaker are mounted, side by side, without leaving space between each to consent free air circulation on the breaker sides, and have simultaneous operation, the thermal trip adjuster must be positioned at a value 15% greater than the rated motor current. | | |
| | | 11 SM3A... | | |
| | | |
| | | |
| | | Breaking capacity | | |
| | | |
| | | Type | | Rated short-circuit breaking capacity [kA] | | Protection fuses when I > Icu (gL or gG fuses) © | | |
| | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | 230V | | 400V | | 500V | | 690V | | 230V | 400V | 500V | 690V | | | | | Icu | Ics | Icu | Ics | Icu | Ics | Icu | Ics | [A] | [A] | [A] | [A] | | | | SM2A 64 | 100 | 100 | 50 | 25 | 10 | 5 | 4 | 2 | ▲ | 125 | 100 | 63 | | | | SM2A 68 / SM2A 72 | 100 | 100 | 50 | 25 | 10 | 5 | 4 | 2 | ▲ | 160 | 100 | 63 | | | | SM2A 76 | 100 | 100 | 50 | 25 | 10 | 5 | 4 | 2 | ▲ | 160 | 100 | 80 | | | | | | | | SM3A 84 | 100 | 100 | 50 | 25 | 12 | 6 | 6 | 3 | ▲ | 160 | 100 | 80 | | | | SM3A88 | 100 | 100 | 50 | 25 | 8 | 4 | 5 | 3 | ▲ | 160 | 125 | 100 | | | | SM3A 92 / SM3A 96 | 100 | 100 | 50 | 25 | 8 | 4 | 5 | 3 | ▲ | 160 | 125 | 125 | | | | | | | | | | | | | | | | | | | | |
| | | |
| | | © Fuses are used only in those cases when the value of short-circuit current at the breaker installation point exceeds the breaking capacity of the breaker. ▲ Industrial fuse not required. | | |
| | | |
| | | ir | | |
| | | Add-on blocks/Accessories pages 1-8 and 9 | | | Dimensions page D-3 | | Wiring diagrams page W-2 | | Technical characteristics page TC-2 | | |
| | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |