-2 Motor protection circuit breakers EE3S
1 _electric
With thermal and magnetic trip releases
Motor protection circuit breakers SM1 up to 32A
Order code
Thermal trip
adjustment range
Short breaki capaci at 400 Icu
ircuit
g y
V
Ics
Qty per pkg
Wt
[A]
[kA]
[kA]
[kg]
Breaking capacity Icu 50kA at 400V.
11 SM1A 40
9-14
50
25
5
0.270
11 SM1A 44
13-18
50
25
5
0.270
11 SM1A 48
17-23
50
25
5
0.270
11 SM1A 52
20-25
50
25
5
0.270
11 SM1A 56
24-32
50
25
5
0.270
Breaking capacity Icu 100kA (0.1-10A) / 25kA (9-32A) at 400V.
11 SM1B 00
0.1-0.16
100
100
5
0.270
11 SM1B 04
0.16-0.25
100
100
5
0.270
11 SM1B 08
0.25-0.4
100
100
5
0.270
11 SM1B 12
0.4-0.63
100
100
5
0.270
11 SM1B 16
0.63-1
100
100
5
0.270
11 SM1B 20
1-1.6
100
100
5
0.270
11 SM1B 24
1.6-2.5
100
100
5
0.270
11 SM1B 28
2.5-4
100
100
5
0.270
11 SM1B 32
4-6.5
100
100
5
0.270
11 SM1B 36
6.3-10
100
100
5
0.270
11 SM1B 40
9-14
25
12.5
5
0.270
11 SM1B 44
13-18
25
12.5
5
0.270
11 SM1B 48
17-23
25
12.5
5
0.270
11 SM1B 52
20-25
25
12.5
5
0.270
11 SM1B 56
24-32
25
12.5
5
0.270
Breaking capacity Icu 100kA (0.1-10A) / 25kA (9-32A) at 400V Suitable for mounting in modular consumer switchboards O.
11 SM1C 00O
0.1-0.16
100
100
5
0.270
11 SM1C 04O
0.16-0.25
100
100
5
0.270
11 SM1C 08O
0.25-0.4
100
100
5
0.270
11 SM1C 12O
0.4-0.63
100
100
5
0.270
11 SM1C 16O
0.63-1
100
100
5
0.270
11 SM1C 20O
1-1.6
100
100
5
0.270
11 SM1C 24O
1.6-2.5
100
100
5
0.270
11 SM1C 28O
2.5-4
100
100
5
0.270
11 SM1C 32O
4-6.5
100
100
5
0.270
11 SM1C 36O
6.3-10
100
100
5
0.270
11 SM1C 40O
9-14
25
12.5
5
0.270
11 SM1C 44O
13-18
25
12.5
5
0.270
11 SM1C 48O
17-23
25
12.5
5
0.270
11 SM1C 52O
20-25
25
12.5
5
0.270
11 SM1C 56O
24-32
25
12.5
5
0.270
General characteristics
The SM1 is a modern series of circuit breakers with thermal and magnetic trip releases and high breaking capacity. Motor control and protection, up to 15kW at 400V, are possible by choosing the suitable adjustment range, 0.1 to 32A.
A magnetic trip indicator integrated on the SM1 breakers avoids dangerous closing operations during short-circuit conditions, previously disconnected by the breaker. The SM1 types are suitable for isolation according to IEC/EN 60947 standards. Their high breaking capacity consents to exclude protection fuses on the majority of the installations.
Operational characteristics
- Rated insulation voltage Ui: 690V
- Rated impulse withstand voltage: 6kV
- Rated frequency: 50/60Hz
- Maximum rated current: 32A
- Number of adjustment ranges: SM1A: 5 (9 to 32A)
SM1B: 15 (0.1 to 32A) SM1C: 15 (0.1 to 32A)
- Breaking capacity: see table below
- Power dissipation: 2.2-9.7W
- Magnetic tripping: 12In max
- Thermal tripping class: 10A
- Phase failure sensitive
- Mechanical life: 100,000 cycles
- Electrical life: 100,000 cycles
- Mounting on 35mm DIN rail (IEC/EN 60715)
- Mounting position: Any
- Utilisation category: A
- Degree of protection: IP20.
Certifications and compliance
Certifications obtained: cULus. Compliant with standards: IEC/EN 60947-1,
IEC/EN 60947-2, IEC/EN 60947-4-1.
11 SM1A...
11 SM1B...
11 SM1C...
NOTE: When more than one breaker are mounted, side by side, without leaving space between each to consent free air circulation on the breaker sides, and have simultaneous operation, the thermal trip adjuster must be positioned at a value 15% higher than the rated
motor current.
O The SM1C version consents to the mounting in enclosures and modular consumer switchboards with minimum depth of at least 45mm between the DIN rail and the opening. See page D-2 for exact breaker dimensions. No front-mount auxiliary contacts 11 SMX11... can be used.
Breaking capacity
Type
Rated short-circuit breaking capacity [kA]
Protection fuses when I > Icu (gL or gG fuses) ©
230V Icu
Ics
400V Icu
Ics
500V
Icu
Ics
690V Icu
Ics
230V
[A]
400V
[A]
500V
[A]
690V
[A]
SM1A 40
100
100
50
25
10
5
4
2
100
80
63
SM1A 44 - 56
100
100
50
25
10
5
4
2
125
80
63
SM1B 00 - 20 SM1C 00 - 20
100
100
100
100
100
100
100
100
SM1B 24 - 28 SM1C 24 - 28
100
100
100
100
100
100
8
8
35
SM1B 32 / SM1C 32
100
100
100
100
100
100
8
8
40
SM1B 36 / SM1C 36
100
100
100
100
42
21
8
8
63
50
SM1B 40 / SM1C 40
100
100
25
12.5
10
5
2
2
80
63
50
SM1B 44 - 56 SM1C 44 - 56
100
100
25
12.5
4
2
2
2
100
80
63
RESET
© Fuses are used only in those cases when the value of short-circuit current at the breaker installation point exceeds the breaking capacity of the breaker. ▲ Industrial fuse not required.
Add-on blocks/Accessories ^ Ç pages 1-4 to 7
Dimensions page D-2
Wiring diagrams page W-2
Technical characteristics page TC-2
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
Contents table
page 1 p.1
page 2 p.2
page 3 p.3
page 4 p.4
page 5 p.5
page 6 p.6
page 7 p.7
page 8 p.8
page 9 p.9
page 10 p.10
page 11 p.11
page 12 p.12
page 13 p.13
page 14 p.14
page 15 p.15
pdf-page pdf di En 2008-11-47-21