Motor protection circuit breakers 1-11
_electric
Add-on blocks and accessories for LMS25 types
Order code
Characteristics
Qty
Wt
per
pkg
[kg]
0
Add-on blocks and accessories
General and operational characteristics
ADD-ON AUXILIARY CONTACTS
- Connectable to right or left side of starter
- Maximum combination: 4 auxiliary contacts
- Rated insulation voltage Ui: 500V
- Conventional free air thermal current Ith: 6A
- Operational current AC15: 3.5A 230V; 2A 400V
- Protection fuse (gL or gG): 6A maximum
- Conductor cross section minimum-maximum (1 or 2 wires): 0.75-2.5mm2
- Width of the auxiliary contacts LMH... equal to 0.5 standard DIN43880 modules.
Add-on auxiliary contacts. Side mount.
11 LMH 01
1NC
10
0.037
11 LMH 10
1NO
10
0.036
11 LMH 11
1NO + 1NC
10
0.042
11 LMH 20
2NO
10
0.037
Undervoltage trip release.
11 LMH...
11 LMU... - 11 LMA...
11 LMU©
To fit inside starter.
10
0.064
For all types
UNDERVOLTAGE AND SHUNT TRIP RELEASES - Must be fitted inside the motor starter.
Shunt trip release.
Undervoltage
Shunt
11 LMA©
To fit inside starter.
10
0.064
For all types
Release range Operating range
0.35-0.7Us 0.85-1.1Us
0.7-1.1Us
Terminal block for busbar supply.
11 SMX90 32
11 SMX90 30
For all types
10
0.033
Three-phase connection busbars 45mm spacing.
THREE-PHASE CONNECTION BUSBAR
11 SMX90 32
For 2 breakers without side-mount contacts
10
0.027
- Imax 63A
- SMX90 3... 45mm spacing to reduce the width to the minimum
- SMX90 4... 54mm spacing to consent to fit one side-mount auxiliary contact block on the breaker
- Conductor cross section minimum-maximum terminal block for busbar supply: 4-25mm2 or 10/4 AWG.
11 SMX90 33
For 3 breakers without side-mount contacts
10
0.048
11 SMX90 34
For 4 breakers without side-mount contacts
10
0.068
11 SMX90 35
For 5 breakers without side-mount contacts
10
0.090
TERMINAL BLOCK FOR BAR SUPPLY
- Imax 63A
- Conductor cross section minimum-maximum:
Three-phase connection busbars 54mm spacing.
11 SMX90 42
For 2 breakers complete with side-mount contacts
10
0.034
4-25mm2or 10/4 AWG.
11 SMX90 43
For 3 breakers complete with side-mount contacts
10
0.054
SURFACE MOUNT ENCLOSURE
- Top or bottom entry:
• M25 threaded knockouts
- Rear entry:
• 15.5mm knockouts
11 SMX90 44
For 4 breakers complete with side-mount contacts
10
0.078
11 SMX90 45
For 5 breakers complete with side-mount contacts
10
0.103
- Up to two auxiliary contact blocks may be mounted
- Earth terminal included
Surface mount enclosures.
- Operating termperature: -5...+40°C
- Storage termperature: -50...+80°C.
11 LMZ 112
IP54. 80mm wide
1
0.220
11 LMZ 111
IP55. 80mm wide
1
0.230
FLUSH MOUNT ENCLOSURE
Flush mount enclosures.
- Window size 70x115mm
- Up to two auxiliary contact blocks may be mounted
- Earth terminal included
11 LMZ 114
IP41. 85mm wide
1
0.150
11 LMZ 113
IP55. 85mm wide
1
0.160
- Operating termperature: -5...+40°C
Accessories for enclosures.
- Storage termperature: -50...+80°C.
Locking mechanism.
ACCESSORIES FOR ENCLOSURES
Locking mechanism:
- Prevents closing operation; 3 padlocks maximum.
11 LMZ 105
3 padlocks maximum
10
0.083
Emergency stop button. IP55 protection.
11 LMZ 106
For all types
1
0.049
Emergency stop button:
- Turn to release
- Red push-button 0 35mm
NOTE: Once mounted on the enclosure, these accessories
Neutral connection.
11 LMN PE
For all types
10
0.010
Pilot light.
raise the degree of protection from IP41 to IP55.
23 NEONV3V
Green
10
0.006
Certifications and compliance
Certifications obtained: GOST; cULus for auxiliary contacts
23 NEONR3V
Red
10
0.006
Spare IP55 membrane complete with rim for enclosures.
and trip releases.
Compliant with standards: IEC/EN 60947-1, IEC/EN 60947-5-1.
11 LMM
For LMZ 11...
enclosures
10
0.002
M25 to PG16 entry adapter.
11 LM M25 PG16
For LMZ111 and LMZ112 enclosures
10
0.009
O Specify rated voltage. Add suffix 60 if frequency is 60Hz. Available voltages:
11 SMX90 30
11 LMZ111 - 11 LMZ112
11 LMZ113 - 11 LMZ114
11 LMZ105 11 LMZ106
24 / 48 / 110 / 220-240 indicate 220 / 380-415 indicate 380 / 440-460 indicate 440 / 480 and 575VAC. © Indicate required voltage value. Available voltages: 24 /110 / 220 / 380VAC.
11 LMNPE
/Ox
23 NEON... V
Y
Dimensions page D-3
Technical characteristics page TC-2