Instrument Specification Sheet:
LM.FlowPod
Display Instrument with Flow rate/Accumulated flow display and linearisation.
Display:
Large 8 digit LCD display with identification of displayed value e.g. ml, litres or m³ - as well as
other functions such as alarm status.
Control panel: Programming by RS485 MODBUS or 3 reed switches operated by external magnets.
Outputs:
Standard 2 channel flow alarm with SPCO relays (rated 240Vac 5A resistive and 3A inductive
loads). Can also be configured for flow status and/or valve leakage. Pulse, 4-20mA, MODBUS as
standard.
Linearisation: 16 data points of linearisation is included for optimization of the flowmeter output characteristic.
Casing: 145 x 125.5 x 110 mm (5.7" x 4.9" x 4.3") L x H x D. Blue, epoxy coated, aluminium.
Mounting: Wall Mounting only;
Operating Temperature: -30°C to +60°C
Power supply: 24 V dc.
Configuration: Configuration is done at SETUP-level programming mode (passworded)
Pulse input:: Litre Meter pulse; TTL (0-5V, up to 0-30V); NPN open collector; PNP and reed switch.
Frequency range: 0.001 – 1999.9 Hz programmable – input up to 2 kHz.
Supply Sensor supply voltage 15V DC - max. 50mA
Instructions: LM05xx
OPERATOR FUNCTIONS:
TOTAL: 13mm minimum character-size - 8 digits. Flow rate & total simultaneously.
Measuring units: ml, litres, gallons, m3, USgal, kg and no unit, many others factory programmable.
Number of decimals: Maximum: four. TOTAL is resettable from the front panel (password protected) or remotely via
the rear terminals. If the unit rolls over 999,999 litres, it will automatically change the display to
1000.00m³.
FLOWRATE: 5 digits;
Time units: Seconds, minutes, hours, days.
Number of decimals: Maximum: Four
Rolling Average: Adjustable - to smooth out flow fluctuations – works on display and outputs.
On-site calibration: Mode to assist user on-site providing display of test time and test pulses counted, control relay
output available.
Programming Includes ability to enter flow and time units; flow points; alarm points and outputs
OPTIONS
/E Analogue Output: 0-5Vdc, 0-10Vdc output etc.
/OC Pulse Output:
/RC relays
Reed switch or open collector output. Scalable in relation to accumulated total: ie/ pulse per X
quantity - pulse on-time adjustable. Reed Switch : volt-free 100Vdc at 0.5A for non-inductive
loads. Max switching power is 10W. max freq 4Hz. Open collector: NPN transistor with emitter
common to 0V. Rated max 100mA 50Vdc 125mW max. internal power dissipation.
/PR Interfacing with a printer
|
|