nt Design - 8200 and 9300 vector
DC fuses
Two ranges of fuses are required to provide DC fuses forthe entire power range of the drive controller.
Industrial fuse size
14*51 mm covers the rated current range from 6 to 40 A
and fuse size 22*58 mm covers the range from 12 to100A.Only
fuse holders of the same size may beinterconnected via DC busbars. DC currents above 100 A can be implemented by connecting 22*58 mm DC fuses in
parallel.Note: A DC busbar system is available for each fuse range.At average supply levels, the current capacity I = 200 A. >
Device14*51 fusewithout signalling deviceFuseTypePower [kW]rated current [A]Order ref. 82110.756EFSGR0060AYHN (2x)82121.510EFSGR0100AYHN (2x) 82132.212EFSGR0120AYHN (2x) 8214 320EFSGR0200AYHN (2x) 8215 4 25EFSGR0250AYHN (2x) 8216 5.532EFSGR0320AYHN (2x)
8217 7.540EFSGR0400AYHN (2x)
8218 1140EFSGR0400AYHN (2x) 82410.3710EFSGR0100AYHN (2x) 8242 0.7510EFSGR0100AYHN (2x) 8243 1.510EFSGR0100AYHN (2x) 8244 320EFSGR0200AYHN (2x) 8245 5.532EFSGR0320AYHN (2x) 8246 1140EFSGR0400AYHN (2x)93210.3710EFSGR0100AYHN (2x)93220.7510EFSGR0100AYHN (2x) 9323 1.510EFSGR0100AYHN (2x)
9324320EFSGR0200AYHN (2x) 9325 5.532EFSGR0320AYHN (2x)
93261140EFSGR0400AYHN (2x)
9341 32EFSGR0320AYHN (2x)9351 20EFSGR0200AYHN (2x) Lenze offers a DC busbar system - EWZ 0036 - for DC fuses 14*51 mm. Lenze
91 >