| | | Design - 8200 and 9300 vector Overview of line protection fuses | | |
| | | |
| | | Operation at 120% overload Line protection fuses with frequency inverter-specific brackets are available for each type of frequency inverter. | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | | | Device | Rated current | Size | Order ref. | Required number | Order ref. | Required number | | | | 8211/8241 /9321EV | M 6A | 10x38 | EFSM-0060AWE | 3 | EFH10001 | 3 | | | | 8212/8242/9322EV | M 6A | 10x38 | EFSM-0060AWE | 3 | EFH10001 | 3 | | | | 8213/8214/8243/ 9323EV | M10A | 10x38 | EFSM-0100AWE | 3 | EFH10001 | 3 | | | | 8244 / 9324EV | M16A | 10x38 | EFSM-0160AWE | 3 | EFH10001 | 3 | | | | 8215/ 8216/9325EV | M20A | 10x38 | EFSM-0200AWE | 3 | EFH10001 | 3 | | | | 8217/ 8218 8245 / 8246 9326EV | M32A | 14x51 | EFSM-0320AWH | 3 | EFH10002 | 3 | | | | 822179327EV* | T63A | - | - | 3 | - | - | | | | 8222* / 9328EV* | T80A | - | - | 3 | - | - | | | | 8223* / 9329EV* | T100A | - | - | 3 | - | - | | | | 8224* / 9330EV* | T125A | - | - | 3 | - | - | | | | 8225*/9331 EV* | T160A | - | - | 3 | - | - | | | | 8226*/9332 EV* | T200A | - | - | 3 | - | - | | | | 8227* / 9333EV* | T250A | - | - | 3 | - | - | | | | | | | | | | | | | | |
| | | |
| | | * Recommended for standard fuses | | |
| | | |
| | | Dimensions Fuse holder | | |
| | | |
| | | | | | | | | | | | | Type | a [mm] | b [mm] | e [mm] | Fuse dimensions | | | | EFH10001 | 17.5 | 81 | 68 | 10x38 | | | | EFH10002 | 26 | 81 | 68 | 14x51 | | | | | | | | | | | | |
| | | |
| | | Lenze | | |
| | | 53 | | |
| | | |
| | | |
| | | | | | | | | | | | | | | | | |