LENNOX
General data reversible unit - WAH
WAH
200
230
Cooling mode
Cooling capacity (1)
kW
173
204
Absorbed power (1)
kW
78,3
96,2
EER
2,21
2,12
Heating mode
Heating capacity (1)
kW
202
246
Absorbed power (1)
kW
77,1
95
COP
2,62
2,59
Electrical data
Voltage
V/Ph/Hz
400/3/50
Start-up intensity
A
385,8
456,6
Maximum current
A
160,4
195,2
Refrigeration circuit
Number of circuits
Nr
2
2
Compressor
Nr
4
4
Evaporator
Brazed plates
Capacity steps
Nr
CD
Refrigerant charge per circuit
kg
27
32,5
Hydraulic connection
Type
Nr
VICTAULIC
Diameter
Inches
2"
2"
Condenser fan (helicoidal)
Number
Nr
4
4
Nominal airflow
m3/h
76400
74400
Fan speed
rpm
1350
1350
Acoustic
Global sound power level (2)
dB(A)
96
97
Operating limits
Maximum outside air temperature
°C
50
49
Minimum outside air temperature
°C
+6°C as standard and -10°C with "all seasons operation" kit
Maximum inlet water temperature
°C
20
Minimum outlet water temperature
°C
+5°C and -10°C with 30% glycol
(1) Evaprating temperature : 7°C - Air : 35°C / (2) EUROVENT conditions / (3) Evaporating temperature : 7°C