A7: UNITRONIC® BUS and ETHERLINE® - Technical Data
A7
Characteristic impedance Q
Mutual capacitance
(800 Hz) max. nF/km ^|
Peak working voltage in V (not for power purpose)
Test voltage conductor/ conductor Urms. V
Conductor resistance max. Q/km (Data Pair)
Minimum bending radius static in mm
Minimum bending radius flexible in mm
Temperature range °C static
Temperature range °C flexible
UNITRONIC® BUS IBS
static laying
100
60
250
1500
186
8 x D
-
-40 °C up to +80 °C
-
UNITRONIC® BUS FD P IBS
highly flexible application
100
60
250
1500
159.8
-
15 x D
-
-30 °C up to +70 °C
UNITRONIC® BUS Yv IBS
outdoor use/direct burial
100
60
250
1500
186
8 x D
-
-40 °C up to +80 °C
-
UNITRONIC® BUS LD 1
static laying 1
100 - 120
60
250
1500
186
8 x D
-
-40 °C up to +80 °C
-
UNITRONIC® BUS FD P LD
highly flexible application
100 - 120
60
250
1500
159.8
-
15 x D
-
-30 °C up to +70 °C
UNITRONIC® BUS L2/FIP 1 A
static laying
150+/-15
30
250
1500
110
75 mm
-
-40 °C up to +70 °C
-
UNITRONIC® BUS FD P L2/FIP
150+/-15
30
250
1500
133
w/o FC = 65 mm
-30 °C up to +70 °C
highly flexible application
FC = 120 mm
UNITRONIC® BUS Yv L2/FIP
outdoor use/direct burial 1 ^^^^m
150+/-15
30
250
1500
110
100 mm
-40 °C up to +70 °C
-
UNITRONIC® BUS PA
(blue + black), static laying
100+/-20
-
250
1500
44
70 mm
-
-30 °C up to +70 °C
-
UNITRONIC® BUS CAN UL/CSA ^^^^L static laying (0.22 mm2) 1 ^^^^^^^
100 - 120
40
250
1500
186
8 x D
-
-40 °C up to +80 °C
-
UNITRONIC® BUS FD P CAN, UL/CSA
highly flexible application (0.25 mm2)
100 - 120
40
250
1500
159.8
-
15 x D
-
-30 °C up to +70 °C
UNITRONIC® BUS FF 1 ^^^^1
static laying
100
56
300
1500
< 24
15 x D
-
-25 °C up to +80 °C
-
UNITRONIC® BUS CCL
static laying
110
60
300
2000
37.8
15 x D
-
-40 °C up to +70 °C
-
UNITRONIC® Etherline®-H CAT.5
2 pairs
100
48
125
1000
192
42 mm
-
-30 °C up to +80 °C
-5 °C up to +60 °C
UNITRONIC® Etherline®-P CAT.5
2 pairs
100
46
125
1000
186.6
42 mm
-
-30 °C up to +80 °C
-5 °C up to +60 °C
UNITRONIC® Etherline®-H-H
2 pairs
100
46
125
1000
186.6
60 mm
-
-30 °C up to +80 °C
-5 °C up to +60 °C
UNITRONIC® Etherline-H FLEX
2 pairs
100
48
125
1000
284
30 mm
78 mm
-30 °C up to +80 °C
-5 °C up to +60 °C
ETHERLINE® P FLEX 1
2 pairs ^^^^^k
100
48
125
1000
V 284
30 mm
78 mm
-30 °C up to +80 °C
-5 °C up to +60 °C
ETHERLINE®-H CAT.5
4 pairs
100
48
125
1000
192
50 mm
-
-30 °C up to +80 °C
-5 °C up to +60 °C
ETHERLINE®-P CAT.5
4 pairs
100
46
125
1000
186.6
50 mm
-
-30 °C up to +80 °C
-5 °C up to +60 °C
ETHERLINE®-H-H
4 pairs
100
46
125
1000
186.6
55 mm
-
-30 °C up to +80 °C
-5 °C up to +60 °C
ETHERLINE®-H FLEX
4 pairs
100
48
125
1000
284
35 mm
90 mm
-30 °C up to +80 °C
-5 °C up to +60 °C
ETHERLINE®-P FLEX
4 pairs
100
48
125
1000
284
35 mm
90 mm
-30 °C up to +80 °C
-5 °C up to +60 °C
ETHERLINE®Y CAT.5e AWG 22/1
static laying
100
48
125
1000
192
-
78 mm
-30 °C up to +80 °C
-5 °C up to +60 °C
ETHERLINE®Y UL/CSA CAT.5e AWG 22/1
static laying
100
48
125
1000
192
-
90 mm
-30 °C up to +70 °C
-5 °C up to +60 °C

pageCatalog pdf di En 2012-05-22-30