Multi Function Tester - Kyoritsu - #1

/ 2


catalogue search
Multi Function Tester - Kyoritsu
P. 01
Multi Function Tester - Kyoritsu
P. 02
Pages:
Multi Function Tester - Kyoritsu


See other catalogues for Kyoritsu

Text version of the page
Quality and reliability is our tradition.
The top of the range KEW6015 can perform TEN separate test functions and provides all the test functions generally required to verify the safety of electrical installations in full compliance with IEC61557. The KEW6015 can store test results in its on-board memory for later downloading to a computer or printer. Data can be downloaded via the Infra Red Communication Port(IRDA Port). The KEW6015 is software driven and guides the user through the test functions required making the instrument very easy to use. It's numerous features include the ability to conduct 3 or 4 wire earth resistance tests, D-Lok technology to prevent tripping of most passive type RCD's when loop testing and mains voltage and frequency measurement. ■ Features
•Live circuit and wiring connection check LED's
•D-Lok technology on loop test range
•On-board memory to store test results
•Downloading of data via IRDA port
•Auto power off
•Back lit display
•Polarity switch
•Continuity Auto-null
•Auto ramp and auto test on RCD ranges
•Designed to IP54 Rating
•Complies with IEC61557
60 50
60 10 A
6011A
6015
9
Continuity Testing
Continuity Testing
Continuity Testing
Loop Impedance Testing
KYORITSU
Rated Voltage 230V + 10% - 15% (20/200/2000 O) 400V + 10% - 15% (200/2000 O) Voltage Measuring Range 100-260V 100440V (200/2000 O ,200A) Impedance Range 20/200/2000 Q Nominal Test Current 15mA (200/2000 O ) 3A (20 O) Base Accuracy 20f!range±(3%rdg+8dgt)200f!range±(3%rdg+8dgt) 2000f!range±(3%rdg+8dgt)
Measuring Ranges 20/200/2000 Q Autoranging
Measuring Ranges 20/200/2000 Q Autoranging
Measuring Ranges 20/200Q Autoranging
ISO 9001/EN 29001/BS 5750 APPROVED BY BVQI
Open Circuit Voltage > 6V Short Circuit Current > 200mA DC Accuracy ± (1.5%rdg+3dgt)
Open Circuit Voltage > 6V Short Circuit Current > 200mA DC Accuracy ±(1.5%rdg+3dgt)
Open Circuit Voltage > 4V Short Circuit Current > 200mA DC Accracy ± (3%rdg+3dgt)
KB/V
Multifunction Tester
Insulation Testing
Insulation Testing
Insulation Testing
Measuring Ranges
Measuring Ranges
Measuring Ranges
20/200M Q Autoranging Test Voltages 250V.500V and 1000V DC Output Voltage on Open Circuit 250V+40%-0% 500V+30%-0% 1000V+20%-0% Rated Current > 1 mA Accuracy ± (1.5%rdg+3dgt)
20/200/2000MO Autoranging Test Voltages 250V,500Vand 1000V DC Output Voltage on Open Circuit 250V+20%-0% 500V+20%-0% 1000V+20%-0% Rated Current > 1mA Accuracy 0-100M Q ±(2%rdg + 3dgt) 100M O - 2000M O ±(2%rdg + 4dgt)
20/200MQ Autoranging Test Voltage 500V DC
Output Voltage on Open Circuit 570V DC ± 6% Rated Current > 1mA Accuracy ± (3%rdg+3dgt)
Rated Voltage 230V + 10% - 15% (20/200/2000 A) 400V + 10%-15% (200 A) PSC Ranges 200/2000A/20kA Accuracy
PSC accuracy derived from measured loop impedance specification and measured voltage specification
Loop Impedance Tes
Rated Voltage 230V AC ± 10%@ 50Hz Voltage Measuring Range 100-250V @ 50Hz Impedance Ranges 20/2000 Q Nominal Test Current 24A (20 O range) 15mA (2000 O range) Accuracy
Loop Impedance Testing
Rated Voltage 230V AC + 10% - 15%@ 50Hz Voltage Measuring Range 100-250V AC @ 50Hz Impedance Ranges 20/200/2000 Q Nominal Test Current 3A(20nrange),15mA(200nrange),15mA(2000nrange) Accuracy
20 a range ±(3%rdg+4dgt) 200 fi range ±(3%rdg+8dgt) 2000 O range ±(3%rdg+4dgt)
Loop Impedance Te
Rated Voltage:230VAC ± 10%@ 50Hz Voltage Measuring Range 100-250V AC @ 50Hz Impedance Range 20/200/2000 Q Nominal Test Current 25A(20 û range) 1.2A(200 fi range) 1.2A(2000 fi range) Test Period 1/2 cycle(10ms)
Base Accuracy 20 O range ±(3%rdg+5dgt)
RCD Testing
Rated Voltage 230V + 10% Trip Current Settings
15%
20 fi range ±(3°
'ordg+8dgt)2000f!range±(3%rdg+8dgt)
RCD Testing |
RCD X 1/2
10,30,100,300,500,1000mA
RCD X1
10,30,100,300,500,1000mA
RCD X5
10,30,100mA
RCD XDC
10,30,100,300,500mA
RCD XRamp
10,30,100,300,500mA
Rated Voltage 230V AC ± 10%@ 50Hz Trip Current Settings RCD X 1/2 : 5,15,50,150,250mA RCD X 1 : 10,30,100,300,500mA
RCD fast :150mA_
Trip Current Duration RCD X 1/2 X 1 : 2000ms
_RCD fast :40ms_
Accuracy
Trip Current ± 3% of test current at 230V Trip time ± (3%rdg+3dgt)
PSC Testing
Rated Voltage 230V AC + 10% - 15%@50Hz PSC Ranges 200A.2000A and 20kA Accuracy
PSC accuracy derived from measured loop impedance specification and measured voltage specification
^^^lEC 61010-1 CAT. Ill 300V lAccessories
Rated Voltage 230VAC + 10%@ 50 Hz
PSC Range 2000A and 20kA Accuracy
PSC accuracy derived from measured loop impedance specification and measured voltage specification
Trip Current Duration RCD X 1/2.X 1,: XDC: 1000ms RCD X 5,DC (500 and X 1 1000mA):200ms
RCD Testing
Contact Voltage Reading
o
Rated Voltage 230V AC + 10% - 15%@ 50Hz Trip Current Settings RCD X1/2 : 10,30,100,300,500,1000mA RCDX1 :10,30,100,300,500,1000mA RCD X5 : 10,30,100,300mA
(on X 5 range max current 1A) Trip Current Duration RCD X1/2X1 : 2000ms, RCD fast: 50ms Accuracy
Trip current + 10%-0% of test current at 230V Trip time ± (1%rdg+3dgt)
RCD Testing
1.0-100.0V
Rated Voltage 230VAC ± 10%@ 50Hz Trip Current Settings RCD X 1/2 : 10,30,100,300,500mA RCD X 1 : 10,30,100,300,500mA RCD X 5 : 10,30,100,300,500mA Trip Current Duration RCD X 1/2 X 1 : 2000ms RCD X 5 : 200ms fast trip 50ms Accuracy
Trip current + 10%-0% of test current at 230V Trip time ± (2%rdg+3dgt)
General Specifications
Safety Standard IEC 61010-1 CAT.Ill 300V
Pollution degree 2 Withstand Voltage 3700V AC for one minute
_Power Source 8 X 1.5V R6P_
Dimensions 186(L) X167(W)X 89(D)mm Weight 980g approx including batteries
Safety Standard IEC 61010-1 CAT. Ill 300V
Pollution degree 2 Withstand Voltage 3700V AC for one minute
_Power Source 8 X1,5V R6P_
Dimensions 175(L)X115(W)X86(D)mm Weight 780g approx including batteries
o
General Specifications
CE Marking:signifies conformance to EMC directive
(89/336/EEC, 92/31/EEC, 93/68/EEC) and Low Voltage directive (73/23/EEC, 93/68/EEC)
Rated Voltage 230V AC + 10% @ 50Hz Fault Current Ranges 2000A and 20kA Nominal Test Current 1,2A (2000A) 25A (20kA) Fault Current Accuracy Fault Current accuracy derived from measured loop impedance specification and measured voltage specification
_Ranges 200 2000 2000O_
Output Voltage 70V peak to peak square wave _Frequency 720Hz ± 5%_
Safety Standard IEC 61010-1 CAT. Ill 300V
Pollution degree 2 Withstand Voltage 3700V AC for one minute Power Source 8 X 1.5V R6P Dimensions 130(L)X183(W)X100(D)mm Weight 1000g approx including batteries
*Provide Basic, Medium & Sophisticated MFT series.
*Fully meet with the needs of convenient and fast installation works.
*World top-ranking MFT's with the latest standards and regulations.
KYORITSU ELECTRICAL INSTRUMENTS WORKS, LTD.
Digital Multifunction Tester
(D
8205 KEW Demonstration Kit
KEW Demonstration Kit is also available from Kyoritsu to help customers with sales promotion and user training. This single unit can be used to give a demonstration of how to use the Insulation/Continuity, Loop and RCD(ELCB) testers. For more datails contact the overseas sales department of KYORITSU.
10ml
Accuracy ■ 5dgt) 200/2000Q (i
20 Q (±2%rdg
2%rdg + 3dgt)
General Specifications
CD
Safety Standard IEC 61010-1 CAT. Ill 300V
Pollution degree 2 Withstand Voltage 3700V AC for one minute Power Source 8X1,5V R6 or LR6 Dimensions 105(L) X 210(W) X 240(D)mm Weight 1924g approx including batteries
3^
IModel KSLP5 (Model 7132)
IDurable Holdall & Accessory pouch
/T\ Safety Warnings
7098 Distribution board test leads(1 set)
for Loop/PSC/RCD testing
7099 Moulded plug test leads(1 set)
for Loop and RCD testing at sockets 7025 Lead for insulation and continuity testing 7109 Earth resistance test leads(1 set) KSLP5 external earth probe 8032 auxiliary earth spikes 8210 IrDA Adaptor Durable Holdall Accessory pouch Battery 8 X 1.5V R6 or LR6
Please read the "Safety Warnings" in the instruction manual supplied with the instrument thoroughly and completely for correct use.
Failure to follow the safety rules can cause f re, trouble, electrical shock, etc. Therefore,make sure to operate the instrument on a correct power supply and voltage rating marked on each instrument.
The contents of this catalogue may be subject to change without notice.
DISTRIBUTOR
KYORITSU ELECTRICAL INSTRUMENTS WORKS,
No.5-20 Nakane 2-chome,Meguro-ku,Tokyo,152-0031 Japan Phone:81-3-3723-0131 Fax:81-3-3723-0152 URL: http://www.kew-ltd.co.jp E-Mail : info@kew-ltd.co.jp Factories : Uwajima & Ehime
LTD.
Mains Voltage Measurement
6015
10 ini
6050
3in1
601 OA
4 in 1
6011A
5in1
Instruction Manual
03.01 F PRINTED IN JAPAN

pageCatalog pdf di En 2012-02-07-13