See other catalogues for
KÜBLER
You may also be interested in
Text version of the page
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
| | | |
| | (:<Ubler | | |
| | | |
| | | | | |
| | | |
| | | Optical fibre signal transmission | | |
| | | |
| | | Optical fibre transmission system for SSI absolute encoders | | |
| | | |
| | | The system is made up of an optical fibre transmitter and an optical fibre receiver. The optical fibre transmitter converts the electrical signals of a normal absolute encoderwith Synchronous Serial Interface (SSI) into a light signal fortransmission by means of an optical fibre. The receiving module convertsthe optical signal backinto electrical signals. Absolute signals can be transmitted safely through one glass fibre over distances of up to 1500 m. The resolution of 13 bit for a singleturn encoder or 25 bit for a multi-turn encoder can be defined by means of a DIP-switch on the front side of the module. | | |
| | | |
| | | Reliable transmission: Easy installation: • Safe signal transmission up to 1500 m. • Signal transmission via a single glass fibre. • Resists extremely strong electro-magnetic fields. • Resolution of 13 bit or 25 bit can be set via DIP-switch • LED for monitoring of power supply, clock and date • DIN-rail mounting - requires min. installation space - only 22 mm wide. | | |
| | | |
| | | Application areas: • Processcontroltechnologyandautomationtechnology • Plantwithlongtransmissiondistances • Interference-sensitiveapplications • Potentialseparation • Highvoltageplant • Hazardousareas | | |
| | | |
| | | Order code: Scope of delivery: • Optical fibre module Optical fibre transmitter: . Multilingual operating manual UB = 10...30VDC LWLS.A1 UB = 5VDC LWLS.A4 Optical fibre receiver: UB = 10...30VDC LWLE.A1 UB = 5VDC LWLE.A4 | | |
| | | |
| | | Accessories: Simplex Patch cable ST-ST - Multimode Connector: 2x ST/PC, Faser: 1 x 50/125 Standard lengths: 2m,5m,8m, 10 m, 15 m, 20 m,... (in 5 m steps) | | |
| | | |
| | | Order code: | | |
| | | |
| | | 05.B09-B09-821-LXXX | | |
| | | |
| | | Length in m | | |
| | | |
| | | ST Multimode coupling Barrel: ceramic, slotted 0rdercode:05.LWLK.001 | | |
| | | |
| | | | | |
| | | | | |
| | | | | |
| | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |