CalomaxTM Steam Humidifier Range
Fresh steam outputs from 6-360 kg/hr
Positioning
The Calomax™ humidifier can be positioned adjacent to the air handling unit or at a maximum of 5 metres away, floor mounted or supported by brackets. The steam may be introduced into either the positive or negative side of the system with a pressure range of ± 2000 Pascals.
Steam Injection
Steam is delivered to the AHU via a stainless steel steam lance. For appli­cations that require short evaporation distances the Multisteam lance is also available. Short evaporation distances and fine steam control are a feature of the Calomax™ units.
Water Quality
Easy access is provided for removal of scale that will form in units which are run on a mineralised water supply.
Water supplies containing dissolved solids ultimately form scale within the steaming chamber and access is provided for the removal of scale as found necessary. In hard water areas where water is softened by a base exchange process, the rate of scale deposit is reduced.
A JS PureFlo™ reverse osmosis system removes up to 99% of dissolved solids in the water. When the CalomaxTM is used with a mains water supply, the JS PureFloTM will greatly reduce the amount
of scale produced and significantly extend the periods between servicing.
Hygienic and Safe
All parts of the JS Calomax™ in contact with steam or water are manufactured from stainless steel, nickel plated copper, tinned copper, tinned gunmetal or other non-corrosive materials for maximum hygiene and safety.
In addition, there's an automatic drain and flush cycle operated by a timer which effectively industrial drains and renews the water periodically. This feature prevents scumming and foaming and ensures efficient operation at all times.
Multisteam short evaporationsteam lance
Features
Compact, self generative units
Suitable for air pressures ± 2000 Pascals
Stainless steel steam lances
Easily installed and maintained
Automatic timer operated drain and flush
Available in intrinsically safe versions
• •
$0%
JS PureFlo reverse osmosis unit
Steam Outputs
H.T.H.W mean
°C
116
127
134
142
144
149
temperature
°F
240
260
274
287
292
298
Raw steam
Bar
0,69
1,38
2,07
2,76
3,10
3,4/6,9
pressure
P.S.I.
10
20
30
40
45
50/100
HT100
Output kg/hr
6
15
26,5
36,5
41
45
HT200
Output kg/hr
12
30
50
70
75
80
HT400
Output kg/hr
28
59
100
145
164
180
HT800
Output kg/hr
57
118
200
290
327
360
Clean steam where HTHW or raw steam is available
Benefits
the system is suitable for mains, softened or reverse osmosis water.
Where appropriate supplies of high temperature hot water or raw boiler steam are available, the Calomax™ range is the natural choice of humidifier for large air handling systems.
Even in those industries where raw boiler steam is inappropriate for production or humidification use, the Calomax™ steam humidifier can be used with complete confidence. Pure sterile steam is produced safely at virtually zero additional cost.
The Calomax™ humidifier range operates from either high temperature hot water or raw boiler steam.
It is available in four models with outputs ranging from 6 to 360 kg/hr of pure, sterile steam, depending on input temperature or raw steam pressure.
The Calomax™ humidifier is totally hygienic and safe. It can be fitted adjacent to the air handling unit or located up to 5 metres away. Steam is piped via flexible steam industrial hoses and uses standard steam lances.
Any type of input water may be used and
Low cost pure sterile steam
No carry-over of impure raw boiler steam
Hygienic and safe in use
Virtually noiseless
Easily installed into existing air handling units
Low maintenance options save money & time
Notes
Mean high temperature hot water (HTHW) temperature at actual point of connection to humidifier after taking into account the temperature drop through industrial control valves. Valves and pipelines sized to pass 0.89kW of primary heat for each 1.0kg/hr of fresh steam to be evaporated. Pressure drops through industrial humidifiers available upon request.
Raw steam pressure at actual point of connection to humidifier after taking into account the pressure drop through control valves. Valves and pipelines sized to pass 1.4kg of raw boiler steam for each 1.0kg/hr of fresh steam to be evaporated.
www.jshumidifiers.com
JS has a policy of continually improving products and performance. Actual specifications might vary from those shown.
JS Humidifiers pic
Artex Avenue, Rustington, LITTLEHAMPTON, West Sussex, BN16 3LN, UK.
Tel: +44 (0)1903 850200 • Fax: +44 (0)1903 850345 email: sales@jshumidifiers.com
0
humidity croup
ISO9001
REGISTERED COMPANY
ISO14001
REGISTERED COMPANY
www.jshumidifiers.com
JS Humidifiers plc
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
pdf-page pdf di En 2008-10-42-14