| | | Model J3-2910 | | |
| | | |
| | | Doc: J3/29I0/0I March 2007 | | |
| | | |
| | | Highly visible LED light gives continuous actuator status indication. J3 L - 12-24V AC/DC J3 H - 80-240V AC/DC Multi-voltage capable with auto-voltage sensing: Torque output: range: 25~95Nm Break 20~80Nm Reseat Electronic torque limiter Protects against valve jams Anti-condensation heater Manual override All connections via external DIN plugs ~ no need to remove cover to connect Volt free end of travel confirmation switches IP65 weatherproof housing CE marked Traceable sequential serial numbering system Optional failsafe kit (Battery Back-up) - actuator fails to safe position on power failure Optional modulating kit with digital positioning system, either 0-10V or 4-20mA | | |
| | | Electrically operated 6,000 psi 3 way L port 316SS ball valve | | |
| | | |
| | | Reduced bore 6,000 psi rated 3 way 316 stainless steel L port ball valve, PVDF seats, ends screwed BSP, fitted via stainless steel mounting kit with J3 electric actuator. Supplied assembled and dry bench function tested. Size range from 1/4" to 1". Available with NPT ends. | | |
| | | |
| | | Type Function J3-29I3 Standard power to open - power to close - Stays put on mains failure J3-29I4 Failsafe BSR - Battery Spring Return - Fails to safe position using an internal battery J3-29I5 Modulating DPS - Digital Positioning System | | |
| | | |
| | | Applications: Water, oil and many corrosive medias, subject to compatibility with wetted parts in contact with media. Actuators sized on a maximum differential pressure of 200 bar wet service, if the intended duty is above this differential, or dry (air or gas) call to check actuator sizing as a larger output actuator may be required. Maximum working temperature of assembly is +I30C. If the intended duty is a higher temperature than this, call to discuss seat and mounting kit options. | | |
| | | |
| | | Flow path: 'L' port (diverting) onl | | |
| | | Valve Specifications: Body Ball Seats Pressure rating Valve temp limits Actuator temp limits | | |
| | | |
| | | 3I6SS SII 3I6SS SII PVDF 6000 psi -30 to +I50°C -20 to + 70°C | | |
| | | |
| | | |
| | | Inlet The LED flashes on/ off When the actuator senses an impending valve jam, the electronic torque limiter is activated and on activation, repeatedly flashes the LED on and off. | | |
| | | Status light basic functions: Constantly lit LED If the actuator is operating correctly with no faults, the LED shows a constantly lit light. | | |
| | | The LED flashes with 2 blinks If the actuator has been left in 'manual' mode, the actuator's motor runs but doesn't drive the output shaft. After a pre-set time, the actuator knows that as the torque limiter has not activated and that the motor is running, it must be in manual. | | |
| | | |
| | | |
| | | |
| | | Qaaacici aaaaaa aaaacü: | | |
| | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | |