Model J3-2910
Doc: J3/29I0/0I March 2007
Quick guide to the J3 electric actuator standard features :
Highly visible LED light gives continuous actuator status
indication.
J3 L - 12-24V AC/DC J3 H - 80-240V AC/DC
Multi-voltage capable with auto-voltage sensing:
Torque output: range: 25~95Nm Break 20~80Nm Reseat
Electronic torque limiter Protects against valve jams
Anti-condensation heater
Manual override
All connections via external DIN plugs ~ no need to remove cover to connect
Volt free end of travel confirmation switches
IP65 weatherproof housing CE marked
Traceable sequential serial num­bering system
Optional failsafe kit (Battery Back-up) - actuator fails to safe position on power failure
Optional modulating kit with digital positioning system, either
0-10V or 4-20mA
Electrically operated 6,000 psi 3 way L port 316SS ball valve
Reduced bore 6,000 psi rated 3 way 316 stainless steel L port ball valve, PVDF seats, ends screwed BSP, fitted via stainless steel mounting kit with J3 electric actuator. Sup­plied assembled and dry bench function tested. Size range from 1/4" to 1". Available with NPT ends.
Type Function
J3-29I3 Standard power to open - power to close
- Stays put on mains failure J3-29I4 Failsafe BSR - Battery Spring Return
- Fails to safe position using an internal battery J3-29I5 Modulating DPS - Digital Positioning System
Applications:
Water, oil and many corrosive medias, subject to compatibility with wetted parts in contact with media. Actuators sized on a maximum differential pressure of 200 bar wet service, if the intended duty is above this differential, or dry (air or gas) call to check actuator sizing as a larger output actuator may be required.
Maximum working temperature of assembly is +I30C. If the intended duty is a higher temperature than this, call to discuss seat and mounting kit options.
Flow path: 'L' port (diverting) onl
Valve Specifications:
Body
Ball
Seats
Pressure rating Valve temp limits Actuator temp limits
3I6SS SII 3I6SS SII PVDF 6000 psi -30 to +I50°C -20 to + 70°C
Inlet
The LED flashes on/ off
When the actuator senses an impending valve jam, the elec­tronic torque limiter is acti­vated and on activation, repeatedly flashes the LED on and off.
Status light basic functions: Constantly lit LED
If the actuator is operating correctly with no faults, the LED shows a constantly lit
light.
The LED flashes with 2 blinks
If the actuator has been left in 'manual' mode, the actuator's motor runs but doesn't drive the output shaft. After a pre-set time, the actuator knows that as the torque limiter has not activated and that the motor is running, it must be in manual.