J.Dittrich Elektronic GmbH & Co. KG MF010-O-LC • For monitoring containers • Ambient temperature -10 to +50° C • Waterproof plastic housing, IP65 • 1 analog output (4-20 mA or 0-10 V) and 1 digital output • Fail-safe operation possible • Supply voltage 24 V DC ± 5 % • Standard measuring range: 0.1 to 25 vol% O
2 ± 2% FS • Length of bar probe approx. 220 mm BN1.000.043 • Length of bar probe approx. 400 mm BN1.000.038 1.2Carbon dioxide measuring systems For monitoring indoor air quality. With a novel two-beam infrared measuring system (NDIR) specifically for CO
2 . Air quality signal (MF420-IR-Mobile) • For window-ventilated rooms • Ambient temperature -10 to +50° C • Plastic housing, IP30 • Power supply unit, 230 V DC • 3 LEDs display indoor air quality: green (good, 2,500 ppm). • Icons and acoustic signals facilitate readings • Maintenance-free in normal applications • Standard measuring range: 0 to 3,000 ppm CO
2 ± 2% FS • BN1.001.040 • With integrated data logger: BN1.001.043 MF420-IR-LC • For rooms with a ventilation system • Ambient temperature -10 to +50° C • Plastic housing for wall mounting, IP30 • 1 analog output (4-20 mA) • Maintenance-free in normal applications • Supply voltage 24 V DC ± 5 % • Standard measuring range: 0 to 3,000 ppm CO
2 ± 2% FS • BN1.000.200