20
Electrical features
• Max. 5A
• Maximal operating voltage: 220V AC
• Polarity: 36 + E
• Equipped with silver-nickel butt-contacts
for added reliability and lifetime
• Socket-outlet safety shutter provides IP2X protection with open lid
• Soldered joint max 2.5 mm2
• Only pluggable when disconnected from voltage
• At least 2000 operations can be performed
Mechanical features
• IP65 as soon as the plug is connected
• Casings made of metal protected against corrosion (IK09)
• Operating temperature: -40°C to +60 °
• Cable entry point max. M40
• Interlocking is performed via padlock
Regulatory features
The DXN 37c plugs and socket-outlets can be used
in zones 1 and 2 (gas) and zones 21 and 22 (dust).
They comply with:
• The ATEX 94/9/CE directives
• The EN 60079-0, EN 60079-7, EN 61241-0 and EN 61241-1
european harmonised standards
• The IEC 60079-0, IEC 60079-7, IEC 61241-0 and IEC 61241-1
international standards
Multicontact plugs and
socket-outlets, IP 65,
'e' protection for
explosive atmospheres
(ATEX), comply with
BECMA international
standard.
Specification
DXN37c
Applications
• Power supply to machines and equipment
in explosive atmospheres
• For command and control purposes, i.e.
· Wastewater treatment
· Tunnel equipment
· Refineries
· Engineering