catalogue search
|
You may also be interested in
Filter, Transducer, Transformer, Surge suppressor, Time delay relay
Text version of the page
49
Contactors
IK INSTALLATION CONTACTORS
IKA20, IKD20, IK21, IKA25, IKD25, IK40, IK63
SWITCHING OF LAMPS
Type Power (W) Current (A) C (ěF)
Max. number of lamps per pole at 230 V 50 Hz
IKA20 IKD20 IKA25 IKD25
Fluorescent lamps
- parallel correction
11 0,16 3,5 9 9 10 10
18 0,37 4,5 7 7 8 8
24 0,35 4,5 7 7 8 8
36 0,34 4,5 7 7 8 8
58 0,67 7,0 4 4 5 5
65 0,67 7,0 4 4 5 5
85 0,80 8,0 3 3 4 4
Fluorescent lamps with
electronic control gear
(ECG)
18 0,09 - 25 25 35 35
36 0,16 - 15 15 20 20
58 0,25 - 14 14 19 19
2 x 18 0,17 - 2 x 12 2 x 12 2 x 17 2 x 17
2 x 36 0,32 - 2 x 7 2 x 7 2 x 10 2 x 10
2 x 58 0,49 - 2 x 7 2 x 7 2 x 9 2 x 9
High-pressure
mercury-vapour lamps
- uncorrected
50 0,61 - 14 14 18 18
80 0,80 - 10 10 13 13
125 1,15 - 7 7 9 9
250 2,15 - 4 4 5 5
400 3,25 - 2 2 3 3
700 5,40 - 1 1 2 2
1000 7,50 - 1 1 1 1
High-pressure
mercury-vapour lamps
- parallel correction
50 0,28 7 4 4 5 5
80 0,41 8 4 4 5 5
125 0,65 10 3 3 4 4
250 1,22 18 1 1 2 2
400 1,95 25 1 1 1 1
700 3,45 45 - - - -
1000 4,80 60 - - - -
Metal halide lamps
- uncorrected
35 0,35 - 18 18 22 22
70 1,00 - 10 10 12 12
150 1,80 - 5 5 7 7
250 3,00 - 3 3 4 4
400 3,50 - 3 3 3 3
1000 9,50 - 1 1 1 1
2000 16,50 - - - - -
Metal halide lamps
- parallel correction
35 0,25 6 5 5 6 6
70 0,45 12 2 2 3 3
150 0,75 20 1 1 1 1
250 1,50 33 - - 1 1
400 2,50 35 - - 1 1
1000 5,80 95 - - - -
2000 11,50 148 - - - -
|