29
Contactors
KNL CONTACTORS
KNL43, KNL63
TECHNICAL DATA MOTOR CONTACTORS
GENERAL
Type KNL43 KNL63
Standards IEC/EN 60947-4-1, IEC/EN 60947-5-1, IEC/EN 60947-1,
UL 508
Approvals GOST
Ambient temperature open
°C
-20 … +60
closed -20 … +45
Storage temperature °C -30 … +80
Mechanical endurance op. c. 3 x 106
Max. mechanical operating frequency with no load c./h 3000
Max. electrical operating frequency AC-3/AC-4/AC-15/DC-13 c./h 600/300/1200/1200
Weight kg 0,93
MAIN CIRCUIT
Rated insulation voltage Ui V 690
Thermal current Ith A 75 85
Rated frequency f Hz 50/60
Rated motor power three-phase 230 V
Pm kW
12,5 15
400 V 22 30
AC-3 690 V 30 40
Nazna~eni tokovi motorjev three-phase 230 V
Ie A
45 63
400 V 45 63
AC-3 690 V 33 45
Rated operational current three-phase 400 V
Pm kW
15 22
AC-4 690 V 18,5 25
Electrical endurance AC-3 / AC-4 op. c. diagram 1 diagram 2
Max. back-up fuse for short-circuit protection gL
Coordination type 2
Iv A 80 125
Terminal capacity
rigid
S mm2
35
flexible 25
Screw M6
Screw head PZ2
Tightening torque Nm 4
AUXILIARY
CIRCUIT
Rated insulation voltage Ui V 690
Thermal current Ith A 16
Rated operational current 230 V
Ie A
6
400 V 4
AC-15 500 V 2
690 V 1
• KNL43/63 contactors are mainly used for switching electric motors
• Possibility of direct connection of the BR43 bimetal relay for protection against
overload and in case of phase failure
• Quick assembly to a 35 mm wide mounting rail in accordance with
EN 60715
• Possibility of mounting the NDL5 snap-on auxiliary switch block with four
auxiliary contacts
• Uniform marking of connection terminals in accordance with EN 50005 and
EN 50011
• Use of the MBL43 mechanical interlock
• Degree of protection IP20
|