You may also be interested in
Vision sensor, Temperature sensor, Sensor, RTD, Light curtain
Text version of the page
evaluation systems
time delay relay 1700
1
functions and time ranges adjustable
via DIP-switch
large time ranges with high repeat accuracy
2 integrated relays / change-over contacts
remote control via remote potentiometer
wide range power supply
DIN-housing for mounting on DIN-rail
LED function display
multi-function time delay relay
8 functions and time ranges
description
The DIP switches on the front of the unit are used to set the
times, functions and output relays. Eight functions are available,
see function diagrams. The potentiometer on the
front plate is used for the fine adjustment of the time settings.
The time may be set in eight ranges from 0.1 second
to 300 minutes. Green and red LEDs serve to display the operating
mode. The green LED signals the operational readiness.
The red LED shows the energizing of relay 1. In the
star/delta function the red LED will also light up when relay
2 energizes.
As soon as the operating voltage has been applied the internal
processor loads the function and the fundamental time
range that has been set on the DIP-switches. New settings
on the DIP switches will not become effective until after the
operating voltage has been interrupted and then reapplied.
Time-settings that have been altered through the potentiometer
are acquired during the operation.
mounting and connecting
The housing is mounted on a 35mm DIN-rail. The operating
voltage should be applied to terminals A1 and A2. The make
contacts (terminals 15/16/18 and 25/26/28) of the two
integrated relays can be wired as you like. They operate differently
depending on the selected function. The floating
encoder contact that is required for some functions is connected
to the B1 and B2 terminals. If no floating contact is
available an external control voltage must be connected to
terminal B2 corresponding to the potential on A1.
The remote potentiometer is connected to the terminals Z1
and Z2. The maximum resistance of the encapsulated
potentiometer is 10kÙ. The feed line must be shielded and
earthed and must not be longer than one meter. Any remote
potentiometer that is connected is recognized automatically
by the device after the operating voltage has been
applied.
important notes
for direct current operation connect the positive pole
to terminal A1
terminal B1 has always the same potential as terminal
A1 (possibly supply voltage)
do observe the technical data on the reverse
a remote potentiometer with metal axis must be
earthed
the device may only be operated with the plexiglass
cover in place
after the device has been successfully installed, no
manipulation with tools should be carried out whilst it
is operating
design 22.5 x 75 x 110mm
multi-function time delay turn-on
turn-on, instant
turn-on timed
turn-off
cycle, pulse
cycle, pause
pulse forming
star/delta
ipf electronic gmbh Kalver Straße 27
D-58515 Lüdenscheid
subject to alteration!
version: November 2008
Fon +49 (0) 2351 / 9365-0
Fax +49 (0) 2351 / 936519
www.ipf-electronic.de
E-Mail: info@ipf-electronic.de
|
|