Controllers / Gateways,network extension
Network extension
For industrial
applications
AS-i bus termination. Use at the end of the bus cable. Extends the cable length by a further 100 meters. Improves the AS-i messages by reducing reflections. One bus termination possible per master, one per repeater.
Bus termination
Special features of the units: For more explanations see
the technical glossary chapter starting on page 256
Safe data transmission for extended installations Accessories and connectors AS-i is easy to use. This principle also applies to the bustermination. It can be mounted wherever the AS-i com-
munication is affected by reflections. Reflections can
occur when the yellow AS-i cable is considerably longer
than 100 meters. A bus termination can be used to pre-
vent these reflections. The optimum mounting position
is the point as far as possible away from the AS-i power
supply.With the bus termination cable lengths of up to 200 mcan be achieved. There are two possibilities to check the
signal quality before and after installation of the bus ter-
mination:1. via the diagnostic menu on the controller e. All repeatmessages are analysed and represented there, separately
for each slave.2. with the eASi tester, a service unit which is connectedto the AS-i cable in parallel and evaluates the disturbed
messages by PC and software.
Type Description Orderno. FC-insulation displacement
connector M12, 2-pole E70096 FC-insulation displacement connectorM12, 2-pole, with mounting link AC5005 Further accessories are available starting on page 197 Further connectors are available starting on page 179