AS-i sensors, AirBoxes,valve control,motor starters, RFidentification 5/2-way slide valve - bistable (pulse valve) The 5/2-way function enables triggering of double-acting actuators, e.g.cylinders without return spring.Compared to the monostable valve 2 defined positions are required forbistable operation. In case of a power failure the valve is held in position.

Generalinformation

Addressing

4 [B] 2 [A]

The AirBoxes can be addressed either prior to installation without voltage orwhen connected and wired via the addressing socket integrated in themodule. Only the addressing unit and the corresponding addressing cable with a jack plug are required.

List of articles

Please note

1 [P]3 [R] 5 [S]

When AirBoxes are used filters with at least 5 µm pore size must be used inthe supply of compressed air. The switching elements in the AirBoxes receive a basic lubrication (initial lubrication) so that they can be operated with compressed air which is not lubricated. Important: If in exceptional cases lubricated compressed air is used you must continue to use it as the oil in the compressed air removes the initial lubrication.

Controllers / Gateways, network extension

Diagram of the5/2-way slidevalve - bistable.

Power supplies and earth fault monitors I/O modules for control cabinets

5/3-way slide valve – blocked middle position The 5/3-way function also enables triggering of double-acting actuators,e.g. cylinders without return spring.In contrast to all previously mentioned valves the 5/3-way valve, for example,prevents dropping of a load in the event of compressed air failure due to the blocked middle position. The 5/3-way valve with blocked middle position enables moving back into a defined position in case of an e-stop of the pneumatics.

I/O modules for field applications Safety at Work

Operating princi-ple of the 5/3- way slide valve.

AS-i sensors, pneumatic and actuator solutions

ground

Connection technology Accessories

4 2

Technical information and customer service

53 1

Visit our website: www.ifm-electronic.com