Catalogue Hyfra Pedia - Chilly Compact Water Chiller
www.hyfra.com
print switch display
Page / 2
Manufacturer's
contact details
Where to buy
this product ?
Request
a Quote
HYFRA - 255046, 4943, 14131, 100829, 89308, 96570, 2228, 68084
/ 2
See other catalogues for HYFRA
Text version of the page
Technical data
Cooling capacities
Standard equipment:
Temperatures
Chilly 08
Chilly 15
Chilly 25
Chilly 35
Chilly 45
Ambient air
Water
Cooling capacities in Watt
10
530
920
2100
2740
3750
32° C
15
775
1290
2450
3565
4525
20
1025
1655
2810
4395
5480
10
345
675
1645
2240
3450
37° C
15
615
1050
2060
3080
4395
20
890
1425
2475
3920
5340
10
205
450
1390
1740
3045
42° C
15
480
765
1810
2580
3870
20
755
1085
2230
3420
4690
• Waterlevel control outside
• Stainless steel coil evaporator
• High tech. scroll compressor / low noise
• High efficiency air cooled condensor
• Digital thermostat hysteresis +/-1,0 K
• Refrigerant circuit with TUV approved high pressure switch manufacturer
• Chiller IP 44
• Operating temperature max. 42° C ambient
• Plastic water tank
• Draining through water level control
• Environment friendly refridgerant R 407 c
• Internal by-pass for pump protection
• Non ferrous water circuit
• CE-Standard / ISO 9001 / EN 60204
• Grundfos/Speck pumps
• Water connection quick cuppling
Specifications
Chilly 08
Chilly 15
Chilly 25
Chilly 35
Chilly 45
Refrigerant
R 407 c environment friendly
Power consumption
kW
0,56
2,08
Power consumption max.
kW
0,71
1,11
1,59
2,52
2,98
Current
10,0
12,3
13,3
V/PH/Hz
230/1/50
230/1/50
230/1/50
230/1/50
230/1/50
Air flow rate max.
m3/h
914
1210
1020
2300
2200
Water tank volume
Itr.
18
18
18
30
30
Water flow
l/min.
2,3
10,0
12,9
Water pressure
bar (g)
2,2
3,6
2,9
2,6
2,3
Water connection inlet / outlet
Zoll
3/8
3/8
3/8
Sound pressure (1)
dB (A)
62,2
63,6
64,8
71,7
69,8
Length (L)
mm
755
755
Width (B)
mm
510
510
510
600
600
Height (H)
mm
450
450
450
500
500
Weight (approx.) without water
kg
49
55
65
81
90
Options:
• Water outlet manometer
• Waterlevel switch for pump-protection
• Common alarm (potetial free)
• 2 x water inlet/outlet
• Special voltage
• Autom. fresh water supply
• Non return valve + magnetic valve
(1) Freefield measurement at 1,0 m distance Specifications subject to change
\ Power Supply
Competence and Experience in Industrial cooling stations
DirectIndustry's Virtual Technical Library: PDF Catalogue | Technical Documentation | Brochure | Manual | Industrial directory | Specifications | Characteristics
Search Go
page 1 p.1
page 2 p.2
pdf-page pdf di En 2009-11-48-27