Insulation / Continuity meter with remote probe

Insulation / Continuity meter with remote probe p 1
...
Insulation / Continuity meter with remote probe p 2
Insulation / Continuity meter with remote probe Pag 2 - 3 1. ELECTRICAL SPECIFICATIONS Accuracy is indicated as + (% rdgs + no. of dgt) at 23°C + 5°C, con relative humidity <60%HR Insulation resistance (DC volta Test voltage (V) Range (M Q) Resolution (M Q) Accuracy 0.01 9.99 0.01 ±(2.0%rdg + 2dgt) 50 10.0 49.9 0.1 50.0 99.9 ±(5.0%rdg + 2dgt) 0.01 9.99 0.01 ±(2.0%rdg + 2dgt) 100 10.0 99.9 0.1 100199 1 ±(5.0%rdg + 2dgt) 0.01 9.99 0.01 250 10.0 99.9 0.1 ±(2.0%rdg + 2dgt) 100 249 1 250 499 ±(5.0%rdg + 2dgt) 0.01 9.99 0.01 500 10.0 99.9 0.1 ±(2.0%rdg + 2dgt) 100499 1 500 999 ±(5.0%rdg + 2dgt) 0.01 9.99 0.01 1000 10.0 99.9 0.1 ±(2.0%rdg + 2dgt) 100999 1 1000 1999 ±(5.0%rdg + 2dgt) Category of measure CAT III 240V to Ground CAT III 415V between inputs Open leads voltage: Short circuit current: Nominal current: 1.25 x nominal test voltage voltage measurement resolution:1V <15mA (peak) for each test voltage ...
Insulation / Continuity meter with remote probe p 3
Insulation / Continuity meter with remote probe  Pag 3 - 3 2. GENERAL SPECIFICATIONS MECHANICAL FEATURES Dimensions: 240 (L) x 160 (W) x 70 (D) mm Weight (batteries included): about 1.2kg Protection ...