Thermal equipment trip TAS
4Pages

{{requestButtons}}

Catalog excerpts

Thermal equipment trip TAS - 1

c€ Thermal equipment trip TAS Manual valve with thermal equipment trip AKT..TAS • Isolate the gas pipeline in the event of a fire • High thermal capacity • AKT..TAS: two fittings in one housing • EC type-tested and certified Product brochure ■ GB 1 Edition 05.141

Open the catalog to page 1
Thermal equipment trip TAS - 2

TAS: the thermal equipment trip shuts off pipelines safely up to 650°C. Thermal equipment trips can be used in industrial and commercial installations, upstream of gas inlet systems, at gas cooker points, instantaneous water heaters and gas boilers. In the event of fire, they isolate the gas pipeline and provide long-term protection against the uncontrolled escape of gas and a potential explosion. Valves AKT..TAS and TAS can be used pursuant to the German Firing System Directive and TRGI (DVGW Code of Practice G 600). AKT..TAS: the spacesaving combination of a manual valve and a thermally...

Open the catalog to page 2
Thermal equipment trip TAS - 3

Kitchen safety equip men t with AKT.R10TA S/A KT. R40TAS Examples of application When a thermal equipment trip TAS or a manual valve with thermal equipment trip AKT..TAS (pursuant to TRGI) is installed, the gas safety system features enhanced fire protection. If the ambient temperature increases to more than 95°C in the gas pressure control (and measurement) system, the thermal equipment trip TAS trips and shuts off the gas supply safely. In the application kitchen safety equipment with AKT..R10TAS/AKT..R40TAS and main gas shutoff device with AKT..F50TAS, the gas supply can be shut off...

Open the catalog to page 3
Thermal equipment trip TAS - 4

Technical data Types of gas: natural gas, town gas and LPG (gaseous). Fuel gases in accordance with DVGW Code of Practice G 260. Thermally controlled tripping at: 95°C, +/-5°C. Closing time: 60 s. Duration of seal (HTR): minimum 60 minutes at 650°C. Leakage: 30 l/h (at a test air pressure of 4 bar). Ambient temperature: -20 to +60°C. Thermal equipment trip TAS In acc. with DIN 3586. Inlet connection: Rp internal thread to ISO 7-1, PN 16 flanged connection to ISO 7005. Outlet connection: Rp internal thread and R external thread to ISO 7-1, PN 16 flanged connection to ISO 7005. Housing:...

Open the catalog to page 4