Configuration31 HP289

Model 214D-1 Batch Controller - 9075 5.2Entering the Batch Parameters

StepDisplayDescriptionTextRef 1 BATCH Set Batch Parameters OPTION Options (if installed)5.3 TEST Check Input Signals5.4 END Exit to normal operation CAL Setup Program Parameters5.1
The following steps are displayed when BATCH is selected. 2 BATCH L Maximum Batch Size which can be entered.3.2 xxxxxx Set to 0 if no limit on batch size.3 AUTO S Automaticrestart feature. Off Disable On Enable xx:xx If enabled, automatically restarts the batchxx:xx (mins:sec) after the end of the last batch.3.2.44 START T Slow start time. xx:xx Time, in minutes:seconds, when Relay 2will energize once the batch has started.3.25 COUNT PREST Prestop Quantity. TheBatch Total counts Up or Down. xxxx Quantity at which Relay 2 will de-energizebefore the end of the batch. (e.g., If the batch quantity is 100 liters and Prest is 2 liters, relay 2 will de-energize after 98 liters.)3.26 dn Count down from the batch quantity.3.2 up Count up from zero.7 T OUT TheSignal Timeout in seconds (Setting to 00 disables this feature.).3.2.28 AOC AutomaticOverrun Compensation. Note that the Signal Timeout must begreater than 0 (i.e., enabled) for this feature to work.3.2.5 En Enable. Dis Disable.