EZE-62
MAXIMUM QUANTITY OF ENTRIES
Thread Size
MI6
M20/Os/O
M20/A
M25
M32
M40
M50
Bottom Face Quantity
60
60
42 (36*)
27 (24*)
18
12
6
* Recommended maximum for cable gland installation.
Technical Data
• Increased Safety EExe. <g> II 2 GD EExe II. EZE-62 Baseefa Certificate No. Baseefa 04ATEX 017IX.
• EZI-62 (Empty) Baseefa Certificate No. Baseefa 04 ATEX 0171U.
• Suitable for use in Zone I, Zone 2, Zone 21 & Zone 22.
• Construction and test standards EN 50014, EN 50019 and EN 50281 -1 -1. IEC 60079-0 and IEC 60079-7.
• IP66 ingress protection to IEC 60529 and EN 60529.
• DTS0I deluge protection witnessed by EECS.
• Operating temperature range -40°C to +80°C. Temperature Class and Ambient T6 40°C. Optional T5 with ambients up to 65°C.
TERMINAL CAPACITY DATA
Terminal Type
Conductor Size (mm2)
Max. Volts
Typical Terminal Arrangements
Min.
Max.
5 Vertical Rails
2Vertical Rails
1 Vertical Rail
Terminal Quantity
Amps
Terminal Quantity
Amps
Terminal Quantity
Amps
WDU 2.5
0.5
2.5
550
190
5
58
10
25
15
WDU4
0.5
4
750
160
7
47
14
21
21
WDU 6
0.5
6
550
120
10
43
18
19
27
WDU 10
1.5
10
550
95
15
37
25
16
37
WDU 16
1.5
16
550
80
21
33(**)
33
15
49
WDU 35
2.5
35
750
60
36
27(**)
54
12
81
Information in the table above is based on the maximum conductor size permitted for the terminal. ** 3Vertical rails are required for the WDU 16 and the WDU 35 terminals.
Notes:
1. A combination of different sized entries is possible, please contact Hawke for more information.
2. The table above gives an indication of potential terminal arrangements. Please contact Hawke for information on other arrangements or empty enclosures.
3. A combination of different sized terminals is possible, please contact Hawke for more information.
4. Other terminal types are available.
HAWKE
International
HWK4I Sept '04
To the best of om is accurate at the right to improveThe company is l omissions that that the prodm
knowledge the information contained in thi ime of going to print and the company r modify any product illustrated without notificati jnable to accept liability for any inaccuracies, error: ay exist. It is the customer's responsibility to ensui is suitable for their application.
et All copyright reserved-Hubbell Ltd 2004. This document anc
pe all copyright therein is the property of: Hawke International a trading name
of Hubbell Ltd (A member of the Hubbell Group of Companies). Copyright Condition:This document shall be used only for the purpose for wr it is provided and no reproduction or publication of the document may be mac and no article may be manufactured or assembled in accordance with informat
contained in the document without prior written consent of the owner.

pageCatalog pdf di En 2012-05-22-29