Enclosure Type Glass Reinforced Polyester PL722
Increased Safety EExe
Technical Data
» Increased Safety EExe. @ II 2 GD EExe II. » PL722 BASEEFA Certificate No.
BAS0I AT EX 2108X. » ZPL722 BASEEFA Certificate No.
BAS0I ATEX2I02U. » Suitable for use in Zone I,Zone 2,
Zone 21 & Zone 22. ► Construction and test standards
EN 50014, EN 50019 and EN 50281 -1 -1.
IEC 60079-0 and IEC 60079-7.
IP66 ingress protection to IEC 60529 and
EN 60529.
* DTS0I deluge protection witnessed by EECS.
* Operating temperature range -20°C to +75°C.
* Temperature Class and Ambient T6 40°C. Optional T5 with ambients up to 65°C.
» Assembly instruction sheet No. A.I. 273.
For PL722. » Assembly instruction sheet No. A.I. 272.
For ZPL722. i Alternative Certification Options Available. * El @ Exe II.
220mm
84mm
206mm Base Fixing CRS
Face A
Face C
2 off 6.25mm Dia. Mounting Holes. Integral Internal to External Earth Connection through Mounting Feet
12m rr
4 off M5 Stainless Steel Socket Head Cap Screws, Key Size-4mm
Approx. weight : 2.0kg
r-.
-J O.
MAXIMUM QUANTITY OF ENTRIES PER FACE
Thread Size
M16/M20
M25
M32
Top & Bottom Faces A & C Quantity
6
4
3
Side Faces B & D Quantity
3
2
1
y A Exe Il/Exe II.
Note: For Cable Entry Positions see page 19.
For full Technical Specification see page 20.
TERMINAL CAPACITY DATA
Terminal Type
Conductor Size (mm2)
Max. Volts
Max. Physical Terminal Content
Reduced Terminal Content at Max. Terminal Amps
Min.
Max.
Terminal Quantity
Amps
Terminal Quantity
Amps
WDU 2.5
0.5
2.5
550
35
9
6
21
WDU 4
0.5
4
750
29
12
5
28
WDU 6
0.5
6
550
22
17
5
36
WDU 10
1.5
10
550
17
25
4
50
Notes: DFor Junction Box Wattage Factor & Combined Terminal Resistance see pages 37 - 39. □ An earth terminal equal to that of the largest power terminal will be fitted.
All copyright reserved-Hitfoell Ltd. This document and all copyricht therein is the property of: Hawke International a cfvisonof Hii±ell Ltd (A merrtoer of the Hubbell Group of Companies).
Copyright ConditionrThis document shall be used only for the purpose for which s provided and no reproduction or publication of the document may be made
To the best of our knowledge the information contained in this leaflet, is accurate at the time of going to print and the company reserves the right to improve or modify any product illustrated without notification. The company is unable to accept liability for any inaccuracies, errors or omissions that may exist. It is the customer's responsibility to ensure that the product is suitable for their application.
H4WKE
I nternational
HWK05 Mar '02
Smarter products www.ehawke.com
uid no
'tide may be manufactured or assembled in accordance with informatioi t without prior written consent of the

pageCatalog pdf di En 2012-05-22-29