2285d Transformer Test System - Haefely Test AG - #1

/ 4


catalogue search
2285d   Transformer Test System - Haefely Test AG
P. 01
2285d   Transformer Test System - Haefely Test AG
P. 02
2285d   Transformer Test System - Haefely Test AG
P. 03
2285d   Transformer Test System - Haefely Test AG
P. 04
Pages:
2285d   Transformer Test System - Haefely Test AG


See other catalogues for Haefely Test AG

Text version of the page
Tettex
TYPE 2285d
Transformer Test System
TECHNICAL SPECIFICATION
General Specifications
Mains supply
Reference conditions Ambient temperature Relative humidity Operating conditions Ambient temperature Relative humidity
Further operating conditions according to IEC 359 recommendations, usage class I. This system is designed in accordance to the safety requirements of VDE 0411/part 1a and IEC 348, Safety class I.
3 x 400V
23 ± 5 °C 45..75 %
0 ± 45 °C
20..80 %
Resistance Measurement
Measuring range 1 |iQ...500 Q
Resolution 0.1 |iQ
Limits of error ± 0.06% rdg ± 1 |iQ
plus approx. 0.02% for test point selector
Conditions:
At reference conditions and test current table
GENERAL
The 2285 is a modern computer controlled test system for Transformer Resistance and Ratio measurement with tap changer control. It also supports all measurements, super­visions, calculations and report functions for Heat run test.
The test point selector and the two power supplies enable measurements at various test configurations on transformers with up to 3 winding systems with 3 phases.
FEATURES
Fully automatic measurement of
■ Winding resistance
■ Turns ratio
with system controlled tap changing
Measuring range
Test
current
10 |iQ ... 100 |iQ
> 25 A
100 iQ ... 10 mQ
> 15 A
10 mQ ... 100 mQ
> 10 A
100mQ ... 1Q
> 5 A
1Q ... 10Q
> 1 A
10Q ... 100Q
> 0.5 A
Supports heat run test by
■ Cold resistance measurement
■ Temperature measurement and supervision during temperature rise
■ Cooling curve measurement
■ Extrapolation
Up to 18 resistance measurement channels Up to 24 temperature measuring channels
Programmable test procedure for sequential measurement of resistance and ratio including tap changer control, fully automatic, without any human interaction.
Measuring cycle time, selectable Settling time, typically
Test Voltage
compliance voltage, twice
Test Current
Type 2285d/100/3 Power Supplies
5...99 s 10...40 sec max. 60 V
max. 100 A 2 x 3 kW
a brand of
Haefely is a subsidiary of Hubbell Incorporated.

pageCatalog pdf di En 2012-05-22-29