HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor OPERATING MANUAL 27215 Turnberry Lane, Suite A Valencia, California 91355, U.S.A. Tel: 1-(661) 775-9575 / Fax: 1-(661) 775-9515 E-mail: sales@h2scan.com Website: http://www.h2scan.com

 Open the catalogue to page 1

HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor OPERATING MANUAL Our Mission Deliver unsurpassed value and optimize green initiatives with our one of a kind continuous hydrogen-specific sensing technology worldwide. Our Value Propositions Enable end-user customers to efficiently and effectively optimize: Electric utility power transformer fleet and other oil-filled assets (Grid) Petroleum refinery and other industrial process control Facility and equipment safety to minimize downtime ...at a much lower total costs of ownership than the competition. Our Strategic Objectives H2scan's technology...

 Open the catalogue to page 2

HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor OPERATING MANUAL

 Open the catalogue to page 3

HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor OPERATING MANUAL IMPORTANT NOTICES READ AND UNDERSTAND THIS OPERATING MANUAL BEFORE OPERATING OR SERVICING THE UNIT LIMITATION OF LIABILITY IN THE EVENT OF A DEFECT IN A PRODUCT, H2SCAN SHALL NOT BE RESPONSIBLE FOR ANY DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING THEREFROM, INCLUDING, BUT NOT LIMITED TO, LOSS OF REVENUE AND/OR PROFIT. Read and understand this operating manual before installing or using the unit. Only use cables from H2scan with this unit. If this equipment is used in a manner not specified by H2scan, the...

 Open the catalogue to page 4

HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor OPERATING MANUAL 1 SPECIFICATIONS Sensitivity Range (hydrogen at 1ATM on a volume basis in air) Response Time Ambient Temperature Storage Temperature Input Power Analog Output Isolated and self-powered 4-20ma Maximum load impedance: 800Ω Relay Contacts Two programmable SPDT relays with both normally open (N.O.) and normally closed (N.C.) contacts. 5A, 240VAC MAX. 5A, 300VDC MAX. GENERAL USE Serial Communication RS422 19,200 bps, No parity, 8 data bits, 1 stop bit, no handshaking Full access to all maintenance and calibration functions via infrared...

 Open the catalogue to page 5

HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor OPERATING MANUAL Figure 1: Control Module Dimensions (in inches) Figure 2: Sensor Module Dimensions (in inches)

 Open the catalogue to page 6

HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor OPERATING MANUAL 2 DESCRIPTION 2.1 SYSTEM H2scan’s HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor provides hydrogen-specific leak detection and measurement for hydrogen concentrations as low as 4000ppm and can be scaled to any concentration up to 5% hydrogen by volume, a range representing 10% to 125% of hydrogen’s lower flammability limit. The system consists of two modules and a wireless remote control. The Sensor Module houses the hydrogen sensor and the Control Module houses the LCD display and I/O. 2.2 SENSOR MODULE The sensor module...

 Open the catalogue to page 7

HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor OPERATING MANUAL WARNING: IT IS NOT THE INTENT OF THIS MANUAL TO SPECIFY MOUNTING LOCATION(S). IT IS THE RESPONSIBILITY OF THE USER AND INSTALLER TO DETERMINE THE PROPER LOCATION(S) FOR HYDROGEN DETECTION BASED UPON THE PARTICULAR USES OF HYDROGEN AT THE INSTALLATION SITE. 3.3 HYDROGEN SENSING CONSIDERATIONS From any given source, hydrogen gas disperses rapidly and generally upward due to the very low density of hydrogen compared to air. Understanding this behavior allows technicians to more effectively position the sensor to detect hydrogen...

 Open the catalogue to page 8

HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor OPERATING MANUAL 3.6 MODULE WIRING The module connectors are of a two piece design in which the wires are screwed into a receptacle in standard terminal block style. The receptacle plugs into a header mounted on board. The Sensor Module connects with the Controller Module with a 16-pin cable. The wiring is point-topoint, so both ends have the same wiring. All wires must be sized to the amperage required. 3.7 SENSOR MODULE WIRING The Sensor Interface printed circuit board has a 16-pin terminal block, J1, for the Sensor Cable connection to the...

 Open the catalogue to page 9

HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor OPERATING MANUAL 3.9 CONTROL MODULE WIRING The Power Board has a terminal block for the connection to input AC power. Some facilities have separate grounds for signal and AC power. If this is the case run the signal ground and chassis ground wires to the appropriate locations. If there is one ground, jumper the chassis ground and signal ground pins together in J2P. Do not connect the DC and AC grounds together if they are to be isolated from each other. Power Board: J2P 4-Pin Terminal Block for the Power Cable Pin Number Function Description...

 Open the catalogue to page 10

HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor OPERATING MANUAL Interface Board: J2 4-Pin Terminal Block for Serial Interface Cable Description Pin TxD- (Device Transmit, Negative) 1 TxD+ (Device Transmit, Positive) 2 RxD- (Device Receive, Negative) 3 RxD+ (Device Receive, Positive) 4 WARNING: BEFORE THE SYSTEM IS POWERED ON IN A HAZARDOUS ENVIRONMENT, TECHNICIANS MUST CONFIRM A COMPLETE SYSTEM INSTALLATION, INCLUDING ALL ELECTRICAL CONNECTIONS AND WIRING, UNUSED CABLE PORTS ARE PLUGGED, AND EXPLOSION PROOF HOUSING LIDS ARE SCREWED ON TIGHT AND LOCKED INTO POSITION. 4 STARTUP Confirm all...

 Open the catalogue to page 11

HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor OPERATING MANUAL Normal atmospheric pressure fluctuations may also manifest as small hydrogen changes. At the factory, the units are typically calibrated at one atmosphere pressure. Performing the field calibration will compensate for altitude induced inaccuracy. 6 DISPLAY The upper row of the LCD indicates a numerical value for the percent hydrogen concentration or peak hydrogen value. The lower row of the LCD is used to display the hydrogen meter, a logarithmic bar graph ranging from 0.001% (10 ppm) to 100% hydrogen by volume. An open box...

 Open the catalogue to page 12

HY-ALERTA™ 2600 Explosion Proof Area Hydrogen Monitor OPERATING MANUAL Set H2 Range – define hydrogen sensitivity range (standard factory setting: 0% to 5% hydrogen by volume) Low H2 Range – lowest level of hydrogen (standard factory setting: 0% hydrogen by volume) to correspond with the low range IDAC setting High H2 Range – highest level of hydrogen (standard factory setting: 5% hydrogen by volume typical) to correspond with the high range IDAC setting Configure IDAC – define analog output range (standard factory setting: 4mA to 20mA) Low Range – low level analog output (standard factory setting:...

 Open the catalogue to page 13