ULTRASONIC TYPE
General Operating Principle
ULS Series switches operate using ultrasonic sound wave propagation. Ultrasonic sound waves are greatly attenuated when transmitted through air. Conversely, when liquid is present, transmission of the sound waves is greatly enhanced. The electronic control unit generates electrical signals that are converted to bursts of ultrasonic energy at the sensor. The ultrasonic bursts are transmitted across the liquid sensing gap. Upon receipt of a valid signal, the solid-state electronics generate a data enable condition, indicating liquid is present. This signal energizes a relay and provides an output condition.
TRANSMITTING CRYSTAL
I—
RECEIVING " CRYSTAL
5
Q_
LU _l
m
I
LU
_l
LU
> LU _l
7
Switch actuates when level reaches halfway point of gap.
Typical Installation
1. Drill a suitable hole in the vessel or pipe wall and tap for 3/4" NPT. In thin walled vessel or material not suitable for threading, weld or braze a bushing to accept the sensor.
2. Screw the sensor in the threaded section and make sure that there is a good seal. Use a pipe compound or sealing tape to avoid excessive tightening. Do not overtighten.
3. Run the power and control wiring cables to the electronics control unit.
Vertical or Horizontal Mounting
Secondary Containment Tanks and Piping Systems
Maintenance
Electronics are
CARRIER I PIPE SECONDARY CONTAINMENT PIPE
SECONDARY CONTAINMENT
- 3/4' NPT FITTING (1/2' NPT OPTIONAL)
constructed with solid­state components and epoxy-potted.
Periodically, check and clean the sensor when used with liquids which cause a coating build-up on the sensor. No other maintenance is required.
If the pipe or vessel to which the unit is mounted is to be steam-cleaned or cleaned with abrasive detergents, remove the entire unit before cleaning by:
3/4' NPT
FITTING
HIGH LEVEL ALARM ■
!=■ lllllll ijljph
(1) Disconnecting the power
TL
SECONDARY CONTAINMENT TANK
PUMP CONTROL -LOW LEVEL ALARM -
at source.
(2) Opening the housing cover.
(3) Removing power and control wiring cables.
(4) Unthreading the sensor. To reinstall, follow installation procedures.
Advantages of GEMS ULS-10 2-Wire Output Switches
1. No A.C. Power
2. No Coaxial Cable Required
3. Up to 1000 ft. or Longer Distance
4. Reduces Installation Cost
J J J J J J J J J
Contents Page Start
ULS-1 Low Power Steel......................................A-34
ULS-10 & ULS-100 10 Amp Switches...........A-35
ULS-11 Low Power Steel....................................A-37
COMPUTER INTERFACE OR
REMOTE CURRENT DETECTOR CIRCUIT
Visit www.GemsSensars.com for most current information.