SIZING THE SSR Once you have identified the series that offers the best modulation for the load, you should consider the following (in
sequence) to select the product:
- connection scheme (single-phase, 3-phase, 3-phase with only 2 controlled phases)
- line voltage
- load power to be controlled (total power in case of 3-phase).
- type of control required (logic or analog)
- any options, such as load diagnostics Single-phase
SSRRVI I=P V 3-phase Star without neutral or delta ("in line", or "closed")Star with neutral"Open" delta Star without neutral or delta ("in line", or "closed") P=(watt) Total power on loadV=(Volt) Line voltage I=rated current* in SSR for sizing *In 3-phase configurations, this is the current in eachbranch of the load. L1 L3L2 L1L2L3 Guidelines for product selection 3-Phase with two controlled phases L1L2L3 LEGEND WARNING:Even if this application works, it causes a large unbalance on the lines during switch on and switch off. 17 |
|