| | | Spectra Switchboards | | |
| | | |
| | | Spectra Series Switchboards | | |
| | | |
| | | Bussed Pull Sections Section has cross bus that connects to adjacent main section bus. Section width and number of lugs are shown in table below. | | Table 2 Cable Bending Space Reference Tabulation (75°C Cable Ampacity Rating Applies) | | |
| | | |
| | | | | | | | | | | | | | | | | | | | | | | | | Conductor | kcmil Size | Lug Space (Inches) | | | | | | | | | | | | Amperes | Lug Qty | AL | CU | 250-600 | 350-800 | Top | Bottom | | | | | 3 | | X | X | | 16 | 20 | | | | 800 | | | X | 20 | 24 | | | | 3 | X | | X | | 18 | 22 | | | | | | | X | 22 | 26 | | | | | | | X | X | | 18 | 22 | | | | 1000 | 3 | | | X | 22 | 26 | | | | X | | X | | 18 | 22 | | | | | | | | X | 22 | 26 | | | | | 3 | | X | X | | 18 | 22 | | | | 1200 | | | X | 22 | 26 | | | | 4 | X | | X | | 19 | 23 | | | | | | | X | 24 | 28 | | | | | 4 | | X | X | | 19 | 23 | | | | 1600 | | | X | 24 | 28 | | | | 5 | X | | X | | 19 | 23 | | | | | | | X | 24 | 28 | | | | | 5 | | X | X | | 19 | 23 | | | | 2000 | | | X | 24 | 28 | | | | 6 | X | | X | | 19 | 23 | | | | | | | X | 24 | 28 | | | | | 6 | | X | X | | 19 | 23 | | | | 2500 | | | X | 24 | 28 | | | | 7 | X | | | X | 24 | 28 | | | | | 8 | X | | X | | 22 | 26 | | | | | 7 | | X | | X | 24 | 28 | | | | 3000 | 8 | | X | X | | 22 | 26 | | | | X | | | X | 24 | 28 | | | | | 9 | X | | X | | 22 | 26 | | | | | 9 | | X | | X | 26 | 30 | | | | 4000 | 10 | | X | X | | 26 | 30 | | | | 11 | X | | | X | 30 | 34 | | | | | 12 | X | | X | | 30 | 34 | | | | | | | | | | | | | | | | | | | | | |
| | | |
| | | | | | | | | | | | Table 1 Pull Section Dimensions | | | | | | Amperes | Number of Lugs per 0 and N1 | Section Width Minim um | Section Depth Minimum | | | | 800 | 3 | | | | | | 1000 | 4 | 25 | 25 | | | | 1200 | 4 | | | | | | 1600 | 5 | 30 | 25 | | | | 2000 | 6 | | | | 2500 | 8 | 35 | 30 | | | | 3000 | 9 | | | | 4000 | 12 | 40 | 35 | | | | 150% Neutral will have one-half the lugs shown, 250-600 kcmil. | | | | | | | | | | | |
| | | co I co | | |
| | | |
| | | AI or Cu wire. Pull Sections Pull section are available in widths and depths from fifteen inches (15") to sixty inches (60") in five inch (5") increments. Twenty inch (20") width is standard. Depth is same as main section. The pull section provides space for pulling and installing cables. It is also used with bottom feed where reverse feed or reverse mounted devices cannot be used. A barrier is provided for service entrance to meet NEC requirements. Busing and lugs are not provided. | | |
| | | |
| | | |
| | | |
| | | Compression Lugs Are Provided For The Following Ampere Ratings At 100kA | | |
| | | |
| | | Anderson VCEL CU-AL Compression | | |
| | | | | | | | | | | Amperes | Short Circuit Bracing | Lugs Per Phase And Neutral | | | | 800A | 100kA | 3 - 4/0-500kcmil | | | | 1000A | 100kA | 4 - 4/0-500kcmil | | | | 1200A | 100kA | 4 - 4/0-500kcmil | | | | | | | | | | |
| | | |
| | | Publications and Reference: See Section 21 for a list of additional product-related publications | | |
| | | |