MOUNTING
Location
The position of installation should not upset normal
ventilation and comfort of personnel. Noise levels
should remain within the local health and safety
regulations. Ensure the free flow of cooling air and take
care to avoid recirculation.
CAUTION—SAFETY:
Do not remove fan guard whilst motors are connected to
power supply.
Mounting in close rooms
In closed rooms sufficient ventilation must exist to
prevent excessive room temperature. It may be
Necessary to install extractor fans and ducts to provide
adequate ventilation.
Mounting in the open air
Installation in the open air may result in high efficiency
for cooler installations. Low ambient temperatures
increase oil viscosity, which may cause excessive
pressures, therefore a by-pass valve should be provided
or alternatively, an additional oil heating system with
pumped circulation may be installed. Electric motors
must be protected against the weather.
Mounting in dirty areas
Mounting in heavily polluted ambient air will result in dirt
deposits on the cooling surfaces causing reduced
cooling efficiency. Therefore in dusty or oily
environments, regular cleaning should be provided (see
maintenance).
Manner of mounting
The mounting is usually with the radiator vertical by
means of feet or similar. If the radiator must lie
Horizontal arrange fan underneath blowing up so debris
can fall away when fan stops.
INSTALLATION
General
GDM air blown cooler installations are usually installed
in the return flow of the fluid circulation system. (A separate
Off-Line cooler/pump circulation system may also
be used see Pump Range).
Preferably the fluid should enter the cooler at the lowest
connection. For smaller sizes where 2 pass radiators
are fitted, the 2 radiators should be connected in series
always entering the radiator at the lowest connection.
Supply and exit pipes should be connected to the cooler
installation so as to be free from strain or vibrations.
In order to diminish possible transference of vibrations,
especially in mobile installations, vibration damping
mountings should be supplied and the connections
made with flexible pipes.
To avoid undue strain on the cooler connections,
support any flats with a spanner when tightening the
flexible fittings.
Impact pressures or intermittent pressure surges must
not exceed the permissible maximum pressure.
Maximum working pressures
Refer To Cooler Data Sheet
Keep well below the stated limits if there are cycle
variations, or frequent fluctuations of pressure in the
cooler line, as often found on presses and other rapid
cycling systems. (see also precautionary measures).
Mounting of coolers with shaft or pulley driven fan
On GDM coolers fitted with shaft or pulley drive, the
Direction of rotation must conform with the arrow of direction
on the cooler installation.
Installation and Operating Recommendations
For GDM—Air Blown Coolers
G.D.M. (Heat Transfer) Limited
Boston Industrial Estate Tel: +44 (0)1889 574880
Power Station Road Fax: +44 (0)1889 575074
RUGELEY Email: info@gdmcoolers.co.uk
Staffordshire
WS15 2HS Website: www.gdmcoolers.co.uk
G.D.M. (Heat Transfer) Limited
Boston Industrial Estate Tel: +44 (0)1889 574880
Power Station Road Fax: +44 (0)1889 575074
RUGELEY Email: info@gdmcoolers.co.uk
Staffordshire
WS15 2HS Website: www.gdmcoolers.co.uk
|
|