SMART WIRELESS THUM ADAPTER
FISHER FIELDVUE DIGITAL VALVE CONTROLLERS
UNLEASH THE FULL POTENTIAL OF YOUR FIELDVUE INSTRUMENTS
The Smart Wireless THUM adapter can transmit the four HART variables and additional HART status information at the user configurable update rate. Access to this new information enables you to fully optimize your operations for improved performance.
Available Variables Important Status Information
Valve Travel Feedback Travel Deviation Alert
Actuator Pressure Travel Sensor Failure
Input Current Pressure Sensor Failure
Target Travel Supply Pressure Alert
Drive Signal Alert
The THUM adapter can also be used to pass along diagnostic tests and large data files. This important valve performance and maintenance information can be viewed and analyzed through AMS Device Manager, AMS ValveLink Software, and the DeltaV™ control system.
In AMS® ValveLink® Software, the status of all FIELDVUE® instruments within the wireless network is displayed along with indicators of potential problems.
INFORMATION AND DIAGNOSTICS WHILE THE VALVE IS OPERATING
The THUM adapter can also be used to give device specific information, such as valve friction, pneumatic leaks (air mass flow test), and instrument problems (I/P and relay integrity test).
TECHNICAL REQUIREMENTS
Voltage drop across THUM: 2.25V @ 4mA; 1V @ 20mA
Power requirement: Loop powered, no batteries
Update rate: 8 seconds - 60 minutes, configurable
Wireless range: 100 meters, typical
Compatibility: DVC6000, DVC2000
FIELDVUE® DVC2000 with GX valve
©Fisher Controls International LLC2009 All Rights Reserved.
Fisher, FIELDVUE, THUM, PlantWeb, AMS, ValveLink, SNAP-ON, and DeltaV are marks owned by one of the companies in the Emerson Process Management business division of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end-user.
Emerson Process Management
301 South 1st Avenue Marshalltown, Iowa 50158 USA T (641) 754-3011 www.EmersonProcess.com
EMERSON.
Process Management
D351737X012 / MV26-CD209 / Mar09