Orifice Capacities for LP-Gas - FISHER REGULATORS - #1

/ 1


catalogue search
Orifice Capacities for LP-Gas - FISHER REGULATORS
P. 01
Page:
Orifice Capacities for LP-Gas - FISHER REGULATORS


See other catalogues for FISHER REGULATORS

Text version of the page
^^^^^^^■Orifice Capacities for Propane
ORIFICE OR DRILL SIZE
ORIFICE CAPACITY BTU PER HOUR, 11-INCHES W.C.
ORIFICE OR DRILL SIZE
ORIFICE CAPACITY BTU PER HOUR, 11-INCHES W.C.
.008
519
51
36531
.009
656
50
39842
.010
812
49
43361
.011
981
48
46983
.012
1169
47
50088
80
1480
46
53296
79
1708
45
54641
78
2080
44
60229
77
2629
43
64369
76
3249
42
71095
75
3581
41
74924
74
4119
40
78029
73
4678
39
80513
72
5081
38
83721
71
5495
37
87860
70
6375
36
92207
69
6934
35
98312
68
7813
34
100175
67
8320
33
103797
66
8848
32
109385
65
9955
31
117043
64
10535
30
134119
63
11125
29
150366
62
11735
28
160301
61
12367
27
168580
60
13008
26
175617
59
13660
25
181619
58
14333
24
187828
57
15026
23
192796
56
17572
22
200350
55
21939
21
205525
54
24630
20
210699
53
28769
19
223945
52
32805
18
233466
BTU per cubic foot = 2516 Specific Gravity = 1.52
Pressure at orifice, inches of water column = 11 Orifice Coefficient = 0.9

pageCatalog pdf di En 2012-05-21-22