Electro-mechanical Timer
(60 x 60 mm)
Dual-frequency Multi-range
With memory (reversed clutch)
E ■H H
H
u
■H
c
<c
u
0) E 1
o
■H
u
0) H LU
Technical Data
Connection and operating diagrams
Supply voltage
24, 48, 110, 220Vac; 50 and 60Hz
24, 48, 110 Vdc (see Accessories on page 12.10)
Supply tolerance ±10%
Power consumption
6,5 VA
Operating factor
100%
Time range values
multi-range:
base 26 (on request bases 22, 23, 24) side times range selector (6 times range)
Minimum time set
1/60 of time full-scale value
Repeatibility accuracy
±0,5% of time full-scale value
Reset time
300 ms
Diagrams
03, 10, 12, 31, 34
Contacts rating
delayed contacts:
6(3)A 250Vac / 30Vdc
instantaneous contact: 2(0,5)A 250Vac / 38Vdc
Operating life
delayed contacts: 3 x 105 operations, cos 91 instantaneous contact: 2,5 x 105 operations, cos 91
Mechanical life
5 x 106 operations
Insulation voltage
1800V/50Hz
Indication
moving pointer
Temperature range
operating: -10°C +55°C storage: -30°C +80°C
Mounting
2 M3 screws fixing plug in socket
Connections
11-pin socket
faston 6.35 mm, only for diagram 12
Protections
housing: IP51 terminals: IP10
Housing
fiberglass reinforced polycarbonate
Overall dimensions
60 x 60 x 114 mm
Weight
290 g
Approvals
ce
Diagram 03 - Delay on energisation - 2 delayed contacts
L
( ) 11-pin socket numbering
S C1 C2
top
11H13lt4_H_3Jt2_H_B
(7) (6) (4) (3)(2)1__I(10)
The S command supplies the timer and starts the time count. When t time has elapsed, C1 delayed contact changes over and after approximately 1/60 of the full-scale value (top), C2 delayed contact changes over. The timer returns to its set point any time that the power is disconnected for at least 0.3 seconds.
Diagram 10 - Delay on energisation - 2 delayed contacts + 1 instantaneous contact
L
( ) 11-pin socket numbering
S
(1)
S
C1 C2
C3
top
11 13 * 3
(7) (6) (4) (3)
7 5 (8) (10)
(2)
N I
The S command supplies the timer and starts the time count. At the same time C3 instantaneous contact changes over. At the end of t set time, C1 delayed contact changes over and after approximately 1/60 of the full-scale value (top),C2 delayed contact changes over. The timer returns to set point any time that the power is disconnected for a time higher than 0.3 seconds.
Diagram 12 - Delay on energisation - 2 delayed contacts + 1 instantaneous contact
S C1 C2 C3
top
ce
N
The S command supplies the timer and starts the time count. At the same time C3 instantaneous contact changes over. At the end of t set time, C1 delayed contact changes over and after approximately 1/60 of the full-scale value (top), C2 delayed contact chan­ges over. The time returns to set point any time that the power is disconnected for a time higher than 0.3 seconds.
7.8
Declaration of conformity
ROHS (Directive 2002/95/CE)

pageCatalog pdf di En 2012-05-21-23