video corpo

2500 kVA Open Generator Set
4Pages

{{requestButtons}}

Catalog excerpts

2500 kVA Open Generator Set - 1

www.FGWilson.com P2500-1 Image for illustration purposes only. Output Ratings Ratings and Performance Data Generating Set Model Standby 2250.0 kVA / 1800.0 kW 2500.0 kVA / 2000.0 kW - / - - / - Prime Rating These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours. Standby Rating These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3). Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2. Perkins® 4016-61TRG3 Alternator manufactured for FG Wilson by: Leroy Somer Alternator Model: LL9224P Control Panel: PowerWizard 1.1+ Heavy Duty Fabricated Steel Circuit Breaker Type: Ratings at 0.8 power factor. Engine Make & Model: Base Frame: 380-415V,50Hz Prime 4000A Option Frequency: 50 Hz 60 Hz Engine Speed: RPM 1500 - Fuel Tank Capacity: - litres (US gal) Fuel Consumption: l/hr (US gal/hr) - Prime 470.0 (124.2) - - Standby 527.0 (139.2) - (100% Load) Available Options FG Wilson offer a range of optional features to tailor our generating sets to meet your power needs. Options include: Upgrade to CE Certification A wide range of Sound Attenuated Enclosures A variety of generating set control and synchronising panels Additional alarms and shutdowns A selection of exhaust silencer noise levels For further information on all of the standard and optional features accompanying this product please contact your local Dealer or visit: www.FGWilson.com Dimensions and Weights Length (L) Width (W) Height (H) Dry Wet mm (in) mm (in) mm (in) kg (lb) kg (lb) 5972 (235.1) 2180 (85.8) 3402 (133.9) Dry = With Lube Oil 14053 (30982) 14488 (31941) Wet = With Lube Oil and Coolant Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1.22. Generating set pictured may include optional accessories. FG Wilson has manufacturing facilities in the following locations: Northern Ireland • Brazil • China • India • USA With headquarters in Northern Ireland, FG Wilson operates through a Global Dealer Network. To contact your local Sales Office please visit the FG Wilson website at www.FGWilson.com

Open the catalog to page 1
2500 kVA Open Generator Set - 2

Engine Technical Data 50 Hz Air Systems No. of Cylinders / Alignment: Air Filter Type: 16 / 60º Vee Cycle: Replaceable Element Combustion Air Flow: m³/min (cfm) 4 Stroke Bore / Stroke: mm (in) - Prime 160.0 (5650) - - Standby 175.0 (6180) - 160.0 (6.3)/190.0 (7.5) Turbocharged Air To Water Charge Cooled Induction: 60 Hz Cooling Method: Water Governing Type: 3.7 (14.9) - 50 Hz 60 Hz 436.0 (115.2) - Electronic Governing Class: Max. Combustion Air Intake Restriction: kPa (in H2O) ISO 8528 G2 Compression Ratio: 13.0:1 Cooling System Displacement: l (cu. in) 61.1 (3730.0) Moment of Inertia: kg...

Open the catalog to page 2
2500 kVA Open Generator Set - 3

Alternator Physical Data Alternator Operating Data Insulation Class: Winding Pitch Code: Ingress Protection Rating: Excitation System: Leroy Somer Voltage Regulation: (Steady state) Wave Form NEMA = TIF: Total Harmonic content LL/LN: Radio Interference: Radiant Heat: kW(Btu/min) Suppression is in line with European Performance Data: Data Item Motor Starting Reactances shown are applicable to prime ratings. *Based on 30% voltage dip at 0.4 power factor. **With optional permanent magnet generator or AREP excitation.

Open the catalog to page 3
2500 kVA Open Generator Set - 4

General Information Documentation A full set of operation and maintenance manuals and circuit wiring diagrams. Generating Set Standards The equipment meets the following standards: BS5000, ISO 8528, ISO 3046, IEC 60034, NEMA MG-1.22. FG Wilson is a fully accredited ISO 9001 company. Warranty All prime equipment carries a one year manufacturer's warranty. Standby equipment, limited to 500 running hours per year, has a two year manufacturer's warranty. For details on warranty cover please contact your local Dealer, or visit our website: FGWilson.com. Dealer contact details: FG Wilson has...

Open the catalog to page 4